{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM50S","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM50S","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM50S","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM50S","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca GV4PEM50S motor circuit breaker, 3-pole, 50 A rated current, 120 kA breaking capacity at 240 V, electronic thermal-magnetic trip, gray RAL 7016.","salesMarkdown":"## 50 A rated current — the motor sizing anchor The line rated current of 50 A sets the motor full-load current ceiling for this TeSys Deca MPCB. That 50 A figure is the continuous rating under IEC 60947-4-1, so it governs the thermal overload protection band — the motor's FLA must fall within the adjustable trip range of the electronic thermal-magnetic trip unit. At 400...415 V AC, the GV4PEM50S covers motor power ratings from 11 kW up to 22 kW depending on the voltage tap. At 660...690 V AC, it reaches 45 kW — a wide power band for a single frame size, which simplifies panel stock for multi-voltage installations. ## 120 kA breaking capacity — where the SCCR headroom lives That places the GV4PEM50S well above typical 10 kA or 18 kA panel SCCR requirements — it can sit at the feeder head without cascading an upstream fuse or breaker for fault current alone. At 480Y/277 V the UL rating is 65 kA, and at 600Y/347 V it drops to 25 kA — still adequate for most North American industrial panelboards. ## Electronic thermal-magnetic trip — two protection layers in one The trip unit combines electronic overload sensing with a magnetic short-circuit element. The magnetic tripping current is fixed at 850 A — that is 17× the 50 A rated current, which means the instantaneous trip rides above motor inrush (typically 6–8× FLA) and only clears on hard faults. Phase failure sensitivity is built in per IEC 60947-4-1. If one phase drops, the electronic overload detects the imbalance and trips before the motor single-phases to destruction — a standard requirement for motor protection, but not every MPCB includes it as a default feature. ## Panel fit — dimensions, terminals, and mounting It operates in any position, which simplifies layout in crowded enclosures where vertical or horizontal mounting is the only option. EverLink BTR screw terminals accept solid copper from 1.5 mm² up to 95 mm² on the bottom and 70 mm² on the top. The clamping torque is 9 N·m for the larger range — the EverLink design maintains contact pressure through thermal cycling, reducing the need for periodic retorquing on high-current motor circuits. ## Durability and environmental ratings That is a solid service life for a motor-starting application — expect the contacts to outlast the motor's overhaul interval in most process lines. IP40 protection keeps out tools and particles over 1 mm — standard for a panel-mounted device. The enclosure also carries IK07 impact resistance and a glow-wire fire resistance of 960 °C per IEC 60695-2-11, so it meets the thermal stress requirements for unmonitored industrial panels.","metaTitle":"Schneider GV4PEM50S TeSys Deca MPCB, 50 A, 120 kA","metaDescription":"Schneider Electric GV4PEM50S TeSys Deca motor circuit breaker, 50 A rated current, 120 kA breaking capacity at 240 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Width":"3.2 in (81 mm)","Height":"6.1 in (155 mm)","Voltage":"690 V AC 50/60 Hz IEC 60947-2","IP Rating":"IP40","Application":"Motor protection","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Electronic Thermal-magnetic","Pollution Degree":"3","Temp Storage Max":"85 °C","Temp Storage Min":"-50 °C","Insulation Voltage Ui":"800 V AC 50/60 Hz IEC 60947-2","Operating Position":"Any position","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-58...185 °F (-50...85 °C)","Utilization Category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical Life Cycles":"20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In","Mechanical Life Cycles":"40000 cycles","Main Product Or Component Type":"Motor circuit breaker","Ambient Air Temperature Operation":"-13...158 °F (-25...70 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,070.40","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/GV4PEM50S/motor-circuit-breaker-tesys-gv4-3p-50a-icu-100ka-thermal-magnetic-multifunction-everlink-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GV4PEM50S/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM50S","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM50S when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}