{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV4PEM80S6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV4PEM80S6","canonicalUrl":"https://aoctrl.com/schneider/GV4PEM80S6","factsUrl":"https://aoctrl.com/api/mcp/products/GV4PEM80S6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GV4 motor circuit breaker, 80 A rated current, 3-pole, electronic thermal-magnetic trip, 120 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.","salesMarkdown":"## 80 A motor circuit breaker, TeSys GV4 frame The GV4PEM80S6 is a 3-pole motor circuit breaker from the TeSys GV4 range, rated 80 A continuous with an electronic thermal-magnetic trip unit. It is listed to UL 60947-4-1 and IEC 60947-4-1, making it suitable for motor protection in both North American and IEC-distribution panels. ## Trip coordination and motor protection The electronic thermal-magnetic trip provides adjustable overload protection (via the TeSys GV4 dial) plus a fixed magnetic trip at 1360 A — 17× In, which avoids nuisance trips on high-inrush motor starts while clearing bolted faults fast. Phase-failure sensitivity per IEC 60947-4-1 is built in, so a lost phase on the line side trips the breaker before the motor single-phases to destruction. Mechanical durability is 40,000 cycles — the breaker is designed for frequent start/stop applications on conveyors, pumps, and compressors. ## Panel fit and environmental ratings Dimensions are 6.1 in (155 mm) high × 3.2 in (81 mm) wide × 4.6 in (116 mm) deep, with a connection pitch of 27 mm without spreaders or 35 mm with spreaders. The gray RAL 7016 housing carries IP40 protection (finger-safe) and IK07 impact resistance, so it withstands incidental tool contact in an open panel. Terminals accept lug/ring connections up to 95 mm² (0.02–0.1 in²) with a tightening torque of 9 N·m.","metaTitle":"Schneider Electric GV4PEM80S6 TeSys GV4 MPCB, 80 A, 120 kA","metaDescription":"Schneider Electric GV4PEM80S6 TeSys GV4 motor circuit breaker, 80 A rated, 120 kA breaking capacity at 240 V. UL/CSA/IEC listed.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Motor Protection Circuit Breakers (MPCB)"],"specifications":{"Color":"Gray RAL 7016)","Depth":"4.6 in (116 mm)","Range":"TeSys Deca","Width":"3.2 in (81 mm)","title":"GV4PEM80S6","Height":"6.1 in (155 mm)","Category":"US10I1122365","Standards":"CSA C22.2 No 60947-4-1 UL 60947-4-1 EN/IEC 60947-4-1 EN/IEC 60947-2","Rated duty":"Continuous IEC 60947-4-1","description":"Motor circuit breaker, TeSys GV4, 3P, 80A, Icu 100kA, thermal magnetic multifunction, lugs terminals","Control Type":"Toggle","Product name":"TeSys GV4","Motor power kW":"37 kW 400...415 V AC 50/60 Hz 45 kW 500 V AC 50/60 Hz 22 kW 400...415 V AC 50/60 Hz 30 kW 500 V AC 50/60 Hz 37 kW 660...690 V AC 50/60 Hz 45 kW 660...690 V AC 50/60 Hz 55 kW 660...690 V AC 50/60 Hz 30 kW 400...415 V AC 50/60 Hz 37 kW 500 V AC 50/60 Hz","Fire resistance":"1760 °F (960 °C) IEC 60695-2-11","lifecycle_stage":"current","Connection pitch":"1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders","Pollution degree":"3","Range of Product":"TeSys GV4","Breaking capacity":"120 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 100 kA 208Y/120 V AC 50/60 Hz UL 60947 100 kA 240 V AC 50/60 Hz UL 60947 65 kA 480Y/277 V AC 50/60 Hz UL 60947 10 kA Icu 660...690 V AC 50/60 Hz IEC 60947-2 25 kA 600Y/347 V AC 50/60 Hz UL 60947","Device short name":"GV4PEM","Poles description":"3P","Tightening torque":"79.7 lbf.in (9 N.m) 0.02...0.1 in² (16...95 mm²) 44.3 lbf.in (5 N.m) 0.002...0.02 in² (1.5...10 mm²)","Climatic withstand":"IACS E10","Device Application":"Motor protection","Line Rated Current":"80 A","Operating altitude":"5000 m","Operating position":"Any position","Trip unit technology":"Electronic Thermal-magnetic","Utilisation category":"Category A IEC 60947-2 AC-3 IEC 60947-4-1","Electrical durability":"14000 cycles AC-3 440 V In/2 7000 cycles AC-3 440 V In","Mechanical durability":"40000 cycles","Mechanical robustness":"Vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 Vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 Shocks 15 gn 11 ms IEC 60068-2-27","Nbr. of units in pkg.":"1","Maximum Operating Rate":"25 cyc/h","Connections - terminals":"Lugs-ring terminals","IK degree of protection":"IK07 IEC 62262","IP degree of protection":"IP40 IEC 60529","Magnetic tripping current":"1360 A","Phase failure sensitivity":"Yes IEC 60947-4-1","Product or Component Type":"Motor circuit breaker","Suitability for isolation":"Yes IEC 60947-1","Power dissipation per pole":"4.6 W","[Ui] rated insulation voltage":"800 V AC 50/60 Hz IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz IEC 60947-2","Ambient Air Temperature for Storage":"-58...185 °F (-50...85 °C)","Ambient air temperature for operation":"-13...158 °F (-25...70 °C)","[Uimp] rated impulse withstand voltage":"8 kV IEC 60947-2","[Ith] conventional free air thermal current":"115 A IEC 60947-4-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/us/en/product/GV4PEM80S6/motor-circuit-breaker-tesys-gv4-3p-80a-icu-100ka-thermal-magnetic-multifunction-lugs-terminals/"},"ai":{"faq":[{"question":"Where can I buy GV4PEM80S6 and how do I get a price?","answer":"The GV4PEM80S6 is available to order through independent distribution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV4PEM80S6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV4PEM80S6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}