{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GV5PB150N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GV5PB150N","canonicalUrl":"https://aoctrl.com/schneider/GV5PB150N","factsUrl":"https://aoctrl.com/api/mcp/products/GV5PB150N","rawCanonicalId":null},"summary":{"shortDescription":"TeSys GV5 motor protection circuit breaker, 150 A, 3-pole, electronic MicroLogic 2.2 M trip unit, 600 V AC.","salesMarkdown":"This GV5PB150N is a 150-amp, three-pole motor protection breaker from the TeSys GV5 line, with an electronic MicroLogic 2.2 M trip unit that keeps a close eye on phase loss and overloads. Out here in the grease, you want something that'll clear a fault fast—it's rated 65 kA at 240 V, 35 kA at 480 V, and 18 kA at 600 V. The lugs accept AWG 14 up to 3/0 copper or aluminum, torqued to 44.3 lbf·in (5 N·m). Unit-mount style, so it bolts directly to the panel without extra adapters. ## Adjustment and protection Thermal adjustment spans 58 to 130 A, so you can dial in the motor's full-load amps without swapping breakers. Phase failure sensitivity is built in, which catches a dropped leg before the windings start smoking.","metaTitle":"GV5PB150N TeSys GV5 Motor Protection Breaker, 150A, 3P","metaDescription":"GV5PB150N motor protection circuit breaker, 150 A, 3-pole, electronic MicroLogic 2.2 M trip unit. 65 kA at 240 V, 600 V rated. Active production, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"4.36 in (110.74 mm)","Width":"4.12 in (104.65 mm)","Height":"6.4 in (162.6 mm)","Category":"US10I1122365","AWG gauge":"AWG 14...AWG 3/0 aluminium/copper","Product name":"TeSys GV5","Mounting Mode":"Unit mount","lifecycle_stage":"current","Breaking capacity":"65 kA 240 V AC 35 kA 480 V AC 18 kA 600 V AC","Poles description":"3P","Tightening torque":"44.3 lbf.in (5 N.m) 0.004...0.1 in² (2.5...95 mm²) (AWG 14...AWG 3/0)","Line Rated Current":"150 A","Trip unit technology":"ElectronicMicroLogic 2.2 M,","Electrical connection":"Lugs, load Lugs, line","Nbr. of units in pkg.":"1","Breaking capacity code":"N","Phase failure sensitivity":"Yes","Product or Component Type":"Motor protection circuit breaker","[Ue] rated operational voltage":"600 V AC","Thermal protection adjustment range":"58...130 A","Ambient Air Temperature for Operation":"104 °F (40 °C)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$755.00 – $1,079.14","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3492c56aaf95bdf0cf0f3bfd8a46afae.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/GV5PB150N/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of GV5PB150N?","answer":"It is rated 150 A continuous, 600 V AC, with a breaking capacity of 65 kA at 240 V AC, 35 kA at 480 V AC, and 18 kA at 600 V AC. The trip unit is electronic MicroLogic 2.2 M, and thermal adjustment range is 58 to 130 A."},{"question":"How do I source GV5PB150N?","answer":"Submit an RFQ for this order code. As an active part in production, we can provide a price and lead-time quote based on current availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GV5PB150N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GV5PB150N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}