{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"GVAS056","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"GVAS056","canonicalUrl":"https://aoctrl.com/schneider/GVAS056","factsUrl":"https://aoctrl.com/api/mcp/products/GVAS056","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys GVAS056 shunt trip release (MX) for GV2-GV3 manual motor starters, 48 V AC 60 Hz control circuit, obsolete status.","salesMarkdown":"The GVAS056 is a shunt trip release (MX) from the TeSys range, designed to remotely trip a TeSys GV2 or GV3 manual motor starter-protector when the control voltage is applied. It operates on a 48 V AC 60 Hz control circuit, with a threshold tripping voltage of 0.75 to 0.2 Un and a control voltage tolerance of 0.7 to 1.1 Un. Rated insulation voltage is 690 V AC per IEC 60947-1, and 600 V AC per UL 60947-4-1 and CSA C22.2 No 60947-4-1 — this sets the maximum voltage the shunt trip can withstand in the circuit, not the operating coil voltage. The 48 V AC coil pulls 14 VA inrush and 5 VA holding, with 10.5 W inrush and 1.6 W holding power. Mechanical durability is 10,000 cycles with GV3P and GV3L breakers, and 30,000 cycles with GV2ME and GV2P units. ## Physical integration Dimensions are 89 mm high, 18 mm wide, and 66 mm deep. It mounts directly onto the side of a TeSys GV2 or GV3 manual motor starter. Screw clamp terminals accept 1 to 2.5 mm² solid or flexible cable (with or without ferrules), and tightening torque is under 1.4 N.m. The on-load factor is 100 %, meaning it can be continuously energized at rated voltage without derating.","metaTitle":"TeSys GVAS056 Shunt Trip Release, 48 V AC 60 Hz, Obsolete","metaDescription":"GVAS056 is a TeSys GV2-GV3 shunt trip release, 48 V AC 60 Hz, 690 V insulation. Now obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"66 mm","Width":"18 mm","Height":"89 mm","Coil Voltage":"48 V AC 60 Hz","Operating Time":"10...15 ms conforming to IEC 60947-1","Product Status":"Active","Insulation Voltage Ui":"690 V AC conforming to IEC 60947-1 600 V AC conforming to UL 60947-4-1 600 V AC conforming to CSA C22.2 No 60947-4-1","Mechanical Life Cycles":"10000 cycles with GV3P and GV3L 30000 cycles with GV2ME and GV2P","Main Product Or Component Type":"Shunt trip release"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5180391b151759a4c095be5bd6699ad2.pdf","sourceUrl":"https://www.se.com/ph/en/product/GVAS056/shunt-release-mx-tesys-gv2gv3-48v-ac-60hz/","alternativesUrl":"https://aoctrl.com/api/mcp/products/GVAS056/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/GVAS056","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/GVAS056 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}