{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"IMDIFL12MC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"IMDIFL12MC","canonicalUrl":"https://aoctrl.com/schneider/IMDIFL12MC","factsUrl":"https://aoctrl.com/api/mcp/products/IMDIFL12MC","rawCanonicalId":null},"summary":{"shortDescription":"VIGILOHM ADVANCED 12 CHANNEL FAULT LOCATOR WITH MODBUS - 100-440VAC/DC","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Range":"Vigilohm","Accuracy":"+/- 15 %","Application":"Marine application Environment - standard application","Display type":"LCD display","Network size":"Large","Response time":"1 s 1/5th of set filtering time 8 s 1/5th of set filtering time 80 s 1/5th of set filtering time","User language":"Spanish German Italian Russian French Chinese English Portuguese","Physical/Depth":"59 mm","Physical/Width":"108 mm","Earthing system":"IT HRG","Physical/Height":"110 mm","Type of network":"1P + N 3P 3P + N","Type of setting":"Alarm threshold: settable per feeder","lifecycle_stage":"unknown","Device short name":"IFL12MC","Physical/Material":"Thermoplastic","Relative humidity":"5...92 %","Operating altitude":"<= 3000 m","Network capacitance":"Highly polluted","Overvoltage category":"III 300 V II 600 V","Conformance/Standards":"IEC 60364-4-41 IEC 61010-1 IEC 60364-5-51 IEC 61557-9 IEC 61557-15 IEC 61326-2-4 UL 61010-1","Information displayed":"Resistance value Capacitance value Evolution of resistance in graph","Physical/Mounting mode":"Flush-mounted (panel) Clip-on (DIN rail)","Power quality analysis":"Transient capture","Connections - terminals":"Power supply: removable screw terminal block0.2...2.5 mm² Output relay: removable screw terminal block0.2...2.5 mm² Toroids inputs: removable screw terminal block0.2...1.5 mm² Communication: removable screw terminal block0.2...2.5 mm² Voltage inputs: removable screw terminal block0.2...2.5 mm²","Electrical circuit type":"Power circuit Control/command circuit","IP degree of protection":"Case: IP20 Front face: IP54","Input/Number of channels":"12","Input/Monitoring function":"Detection of toroids connection automatic Detection of toroids connection manual mode Detection of IM400 injection current permanent","Input/Type of measurement":"History of alarms Network insulation resistance, range: 200 Ohm...250 kOhm Earth leakage capacitance, range: 0.1...15 µF","Mechanical characteristic":"Long-term storage class 1M11 conforming to IEC 60721-3-1 Transport class 2M4 conforming to IEC 60721-3-2 Stationary use class 3M11 conforming to IEC 60721-3-3","Product or component type":"Insulation fault locator","Physical/Mounting position":"Vertical Horizontal","Configurable filtering time":"5 s 40 s 400 s","Input/Network rated voltage":"0...480 V - AC at 45...440 Hz (device connected to phase) 0...830 V - AC at 45...440 Hz (device connected to neutral) 480...1000 V - AC at 45...440 Hz (device connected to phase with PHT1000 subassembly) 830...1000 V - AC at 45...440 Hz (device connected to neutral with PHT1000 subassembly) 0...480 V - DC 480...1000 V - DC (device connected with PHT1000)","Physical/Cut-out dimensions":"92 x 104 mm","Conformance/Pollution degree":"2","Environmental characteristic":"Exposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52 Long-term storage class 1K22 conforming to IEC 60721-3-1 Transport class 2K11 conforming to IEC 60721-3-2 Stationary use at weatherprotected locations class 3K24 conforming to IEC 60721-3-3","Physical/Type of installation":"Indoor","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...70 °C","Communications & Management/Self-test":"Auto test at start and every 5h Remote test Manual","Communications & Management/Response time":"<= 5 s","Power Requirements/Overcurrent protection":"1 A","Power Requirements/Power consumption in W":"10 W","Power Requirements/Power consumption in VA":"26 VA","Communications & Management/Fault event log":"Alarm logs","Communications & Management/Dry contact type":"1 C/O standard or fail-safe","Communications & Management/Local signalling":"Yellow indicator light: insulation fault Yellow flashing indicator light: communication Green/red indicator light: product status Green indicator light: satisfactory insulation LCD display: transient fault","Power Requirements/[Us] rated supply voltage":"100...300 V (LN) AC 50/60 Hz tolerance: +/- 15 % 100...440 V AC 50/60 Hz tolerance: +/- 15 % 80...120 V (LN) AC 400 Hz tolerance: +/- 15 % 100...440 V DC tolerance: +/- 15 %","Communications & Management/Threshold setting":"Alarm: 200 Ohm...200 kOhm","Communications & Management/Alarm optional delay":"0...120 min for signalling circuit","Communications & Management/Signalling circuit voltage":"250 V - AC at 6 A 48 V - DC at 1 A","Communications & Management/Communication port protocol":"Modbus RS485"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$1,658.62 – $4,391.10","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8ac4dc12fa003963d288b140bc4c8806.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/IMDIFL12MC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/IMDIFL12MC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/IMDIFL12MC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}