{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"K8AC-H23PN-FLK","brand":"Omron","brandSlug":"omron","productSlug":"K8AC-H23PN-FLK","canonicalUrl":"https://aoctrl.com/omron/K8AC-H23PN-FLK","factsUrl":"https://aoctrl.com/api/mcp/products/K8AC-H23PN-FLK","rawCanonicalId":null},"summary":{"shortDescription":"Omron K8AC-H23PN-FLK, Type Heater Element Detector, Series K8AC-H, Input Range 20~200A, Output Type Solid State (2), Display LED Red Characters, Communications RS-485 (CompoWay/F), Mounting DIN Rail, Termination Spring Terminal, Voltage Supply 85~264VAC.","salesMarkdown":"## What this detector does that a temperature controller cannot The K8AC-H23PN-FLK is a dedicated heater element detector, not a general-purpose temperature controller. It monitors current through a heater load via an external current transformer (CT) in the 20~200A range and flags a fault when the current drops below a set threshold — meaning an open heater element, a failed SSR shorted open, or a blown fuse. A temperature controller reading a thermocouple will not catch a dead heater until the process drifts; this unit catches it on the next half-cycle. Two solid-state outputs give you separate alarm and normal-status signals — one can trigger a PLC input, the other a panel beacon. The 4-digit red LED display shows the measured current in real time, so a walk-by glance confirms all heaters are drawing load. ## Panel wiring and integration constraints Mounts on standard DIN rail. The spring terminals accept solid or ferruled stranded wire without needing a screwdriver torque check — faster termination in a panel build. Supply range 85~264VAC means it runs on any common plant voltage from 110 V to 240 V without a transformer tap change. RS-485 communication using Omron's CompoWay/F protocol lets a PLC or SCADA poll the measured current and fault status over a multi-drop bus. If you are integrating into a Modbus network, note the protocol mismatch — CompoWay/F is not Modbus RTU, so a protocol converter or gateway is needed at the master side. Operating temperature range -10°C to 55°C covers most indoor electrical enclosures; if the panel sits near a furnace or in a non-conditioned space above 55°C, derate or relocate the unit.","metaTitle":"Omron K8AC-H23PN-FLK Heater Element Detector, 20~200A","metaDescription":"Omron K8AC-H23PN-FLK heater element detector, 20~200A input, RS-485 CompoWay/F, solid-state outputs, DIN rail, spring terminals.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Series":"K8AC-H","Weight":"0.441 lb (200.03 g)","Package":"Bulk","Mounting":"DIN Rail","Output Type":"Solid State (2)","Display Type":"LED - Red Characters","Product Type":"Heater Element Detector","Protocol":"RS-485 (CompoWay/F)","Product Status":"Active","Supply Voltage":"85 to 264VAC","Temp Operating Max":"55 °C","Temp Operating Min":"-10 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/K8AC-H23PN-FLK/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/omron/K8AC-H23PN-FLK","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/omron/K8AC-H23PN-FLK when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}