{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LA1LC070MC","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LA1LC070MC","canonicalUrl":"https://aoctrl.com/schneider/LA1LC070MC","factsUrl":"https://aoctrl.com/api/mcp/products/LA1LC070MC","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys series, undervoltage trip LA1LC070MC, 230...240 V AC 60 Hz control voltage, 0.2 s time delay, set of 10.","salesMarkdown":"The LA1LC070MC is a TeSys-series undervoltage trip (undervoltage release) from Schneider Electric, designed to drop out a contactor or motor starter when the control voltage falls below a set threshold. It is a service part in the 18402-WORLD SERVICE PARTS(CONTROL ACCESS) category, sold as a set of 10 units. Rated for a control circuit voltage of 230...240 V AC at 60 Hz. The threshold tripping voltage is 0.35...0.7 Uc — meaning it will release (trip) when the voltage drops to between roughly 80 V and 168 V on a 240 V nominal line. The 0.2 s time delay prevents nuisance tripping on brief sags, so it won't drop out during a momentary dip that a motor starting transient might cause. Hold-in power consumption is 4 VA AC; inrush at pickup is 8 VA AC. The control circuit voltage limits are 0.8...1.1 Uc, so the coil will pick up reliably at 80% of nominal and hold in up to 110%. ## Deployment Context This undervoltage trip mounts directly onto TeSys D or TeSys F contactors and starters. It's a standard panel component for motor control centers where undervoltage protection is required by code or by the machine safety circuit — typically on conveyor lines, pumps, or compressors where an unexpected restart after a power dip could be a hazard. The LA1LC070MC carries an Active lifecycle status from the manufacturer.","metaTitle":"Schneider Electric LA1LC070MC TeSys Undervoltage Trip, 230-2","metaDescription":"Active TeSys undervoltage trip for 230-240 VAC 60 Hz circuits. 0.2 s time delay, 0.35-0.7 Uc threshold. Set of 10. Order to RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Coil Voltage":"230...240 V AC 60 Hz","Product Status":"Active","Main Product Or Component Type":"Undervoltage trip"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e753a570f6ac1c94fdff2d6bc3d94301.pdf","sourceUrl":"https://www.se.com/uk/en/product/LA1LC070MC/tesys-integral-undervoltage-trip-230-240-v-ac-60-hz-0-2-s/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LA1LC070MC/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LA1LC070MC","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LA1LC070MC when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}