{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LA1LC070U","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LA1LC070U","canonicalUrl":"https://aoctrl.com/schneider/LA1LC070U","factsUrl":"https://aoctrl.com/api/mcp/products/LA1LC070U","rawCanonicalId":null},"summary":{"shortDescription":"Schneider TeSys range, LA1LC070U undervoltage trip, 240 V AC 50 Hz, 0.2 s time delay, set of 10.","salesMarkdown":"The Schneider LA1LC070U is an undervoltage trip module for the TeSys Integral motor starter range — a compact, coordinated starter-contactor-protector package common in panel builds across Europe and Asia. It monitors the control voltage at 240 V AC 50 Hz and trips the starter if the voltage drops below 0.35 to 0.7 times the rated control voltage (Uc), with a deliberate 0.2 s time delay to ride through brief sags without nuisance tripping. The 0.2 s delay is the key spec for a sourcing buyer: it prevents the starter from dropping out on a momentary dip (like a large motor starting elsewhere on the same line), but still clears on a sustained undervoltage that could cause contactor chatter or single-phasing damage. It ships as a set of 10 units, which is the standard packaging quantity for these service-part undervoltage trips — order one line item and you get ten pieces on the shelf. ## Control circuit fit and limits The control circuit voltage limits are 0.7 to 1.1 times Uc (240 V AC), so the trip coil holds in reliably between 168 V and 264 V AC — a standard tolerance band for industrial control transformers. Inrush power draw is 8 VA AC; hold-in power is 4 VA AC — low enough that a typical 100 VA control transformer can power several of these trips plus contactor coils without oversizing.","metaTitle":"Schneider TeSys LA1LC070U Undervoltage Trip, 240 V AC, 0.2 s","metaDescription":"Schneider TeSys LA1LC070U undervoltage trip for Integral motor starters. 240 V AC 50 Hz control, 0.2 s delay, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"240 V AC 50 Hz","Product Status":"Active","Main Product Or Component Type":"Undervoltage trip"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/47c5e376275472da47f5a6677f83505f.pdf","sourceUrl":"https://www.se.com/ie/en/product/LA1LC070U/tesys-integral-undervoltage-trip-240-v-ac-50-hz-0-2-s/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LA1LC070U/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LA1LC070U","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LA1LC070U when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}