{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LA1LC071U","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LA1LC071U","canonicalUrl":"https://aoctrl.com/schneider/LA1LC071U","factsUrl":"https://aoctrl.com/api/mcp/products/LA1LC071U","rawCanonicalId":null},"summary":{"shortDescription":"Telemecanique TeSys Integral, LA1LC071U shunt trip, 240 V AC 50 Hz, instantaneous, without time delay.","salesMarkdown":"The LA1LC071U is a TeSys Integral shunt trip from Schneider Electric's TeSys range — an instantaneous voltage release that trips the parent contactor or circuit breaker when its control voltage is applied or drops below the dropout threshold. Rated for a 240 V AC 50 Hz control circuit, it draws 8 VA inrush and 4 VA hold-in power. The threshold tripping voltage is 0.35 to 0.7 Uc, meaning the release will unlatch the mechanism when the control voltage falls to roughly 84 to 168 V AC. The operating time is 10 ms or more — instantaneous, no intentional delay. The control circuit voltage limits are 0.7 to 1.1 Uc (168 to 264 V AC), so the shunt trip must see at least 168 V to stay latched during normal operation.","metaTitle":"LA1LC071U TeSys Shunt Trip, 240 V AC, Obsolete","metaDescription":"LA1LC071U TeSys Integral shunt trip, 240 V AC 50 Hz, instantaneous. Obsolete — sourced to order against RFQ. 8 VA inrush, 4 VA hold-in.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"240 V AC 50 Hz","Operating Time":">= 10 ms","Product Status":"Active","Main Product Or Component Type":"Shunt trip"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1713c96fd0ceb3307e61bcc1bf329122.pdf","sourceUrl":"https://www.se.com/nl/en/product/LA1LC071U/tesys-integral-shunt-trip-240-v-ac-50-hz-without-time-delay/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LA1LC071U/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LA1LC071U","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LA1LC071U when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}