{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LA1LC072F","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LA1LC072F","canonicalUrl":"https://aoctrl.com/schneider/LA1LC072F","factsUrl":"https://aoctrl.com/api/mcp/products/LA1LC072F","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Integral, undervoltage trip LA1LC072F, 110 V AC 50 Hz, without time delay, instantaneous release.","salesMarkdown":"The Schneider Electric LA1LC072F is an undervoltage trip accessory for the TeSys Integral starter range. It monitors the control circuit voltage and trips the starter instantaneously when voltage drops below the threshold — no intentional time delay. The coil pulls in at 110 V AC 50 Hz (110...120 V AC 60 Hz) and holds with 4 VA; inrush is 8 VA AC. ## Tripping behaviour and control voltage limits The threshold tripping voltage is 0.35...0.7 Uc — meaning the trip engages when line voltage falls to between roughly 38 V and 77 V on a 110 V nominal circuit. The control circuit voltage limits are 0.8...1.1 Uc (88...121 V AC), so the coil stays reliably energized across normal line sags and tolerances. Below the 0.35 Uc floor, the undervoltage release is guaranteed to drop out; above 0.7 Uc it may or may not hold depending on the exact point in the range.","metaTitle":"Schneider LA1LC072F TeSys undervoltage trip, 110 VAC, obsole","metaDescription":"Schneider Electric TeSys Integral undervoltage trip LA1LC072F, 110 V AC 50 Hz, instantaneous release, without time delay. Obsolete status — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Coil Voltage":"110 V AC 50 Hz 110...120 V AC 60 Hz","Product Status":"Active","Main Product Or Component Type":"Undervoltage trip"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2a5bf98cb3deff20daae872939475a89.pdf","sourceUrl":"https://www.se.com/id/en/product/LA1LC072F/tesys-integral-undervoltage-trip-110-v-ac-50-hz-without-time-delay/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LA1LC072F/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LA1LC072F","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LA1LC072F when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}