{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LAD9AP3D1","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LAD9AP3D1","canonicalUrl":"https://aoctrl.com/schneider/LAD9AP3D1","factsUrl":"https://aoctrl.com/api/mcp/products/LAD9AP3D1","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D LAD9AP3D1 control connection module, for direct motor starter GV2ME-GV3P, 18 A per starter / 60 A power circuit, fixed mounting, IP40.","salesMarkdown":"## What This Module Does The LAD9AP3D1 is a control connection module from the TeSys D range, designed to wire the control circuit of a direct motor starter using a GV2ME or GV3P circuit breaker. It carries 18 A per starter and handles 60 A for the power circuit per IEC 60439-1, with a rated insulation voltage of 750 V and operational voltage of 690 V. ## Mounting and Wiring Mounts fixed on a plate or on 2 x 35 mm symmetrical DIN rail — the same footprint as the TeSys D contactor range, so it fits into existing panel layouts without re-drilling. Spring terminals on both control and power circuits: control side accepts 2 x 1.5 mm² flexible with ferrule, or 2 x 2.5 mm² solid; power side takes up to 3 x 25 mm² solid or flexible. ## Sourcing Reality — Obsolete Part We source it through independent surplus channels; quantities are lot-specific and confirmed at RFQ.","metaTitle":"Schneider Electric LAD9AP3D1 Control Connection Module","metaDescription":"Schneider Electric LAD9AP3D1 TeSys D control connection module for GV2ME/GV3P starters. Obsolete, sourced to order. Rated 18 A per starter, 60 A power circuit.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Motor Control Accessories"],"specifications":{"Standards":"IEC 60439-1","Mounting mode":"Fixed","Derating factor":"20 % of Imax GV2 circuit breaker 60 °C","lifecycle_stage":"current","Mounting support":"Mounting plate 2 x 35 mm symmetrical DIN rail","Pollution degree":"3","Range of product":"TeSys D","Device short name":"LAD9","Network frequency":"50/60 Hz","Climatic withstand":"Resistance to incandescent wire: 960 °C conforming to IEC 60695-2-1","[In] rated current":"18 A per starter 60 A for power circuit conforming to IEC 60439-1 60 A per sub-base conforming to IEC 60439-1","Supply maximum power":"0.36 W","Mechanical robustness":"Shocks 11 ms half sine wave acceleration (15 gn) conforming to IEC 60068-2-27 Vibrations 3...100 Hz (0.7 gn) conforming to BV Vibrations 3...100 Hz (0.7 gn) conforming to IEC 60068-2-6 Vibrations 3...100 Hz (0.7 gn) conforming to LR Vibrations 2...100 Hz (4 gn) conforming to BV Vibrations 2...100 Hz (4 gn) conforming to IEC 60068-2-6 Vibrations 2...100 Hz (4 gn) conforming to LR","Connections - terminals":"Control circuit: spring terminal 2 cable(s) 1.5 mm² flexible with cable end Control circuit: spring terminal 2 cable(s) 2.5 mm² flexible Control circuit: spring terminal 2 cable(s) 2.5 mm² solid Power circuit: spring terminal 3 cable(s) 16 mm² flexible with cable end Power circuit: spring terminal 3 cable(s) 25 mm² flexible Power circuit: spring terminal 3 cable(s) 25 mm² solid","IP degree of protection":"IP40","Product or component type":"Control connection module","Minimum clearance distance":"30 mm","Electromagnetic compatibility":"Electrostatic discharge immunity test: , 3, conforming to IEC 61000-4-2 Fast transients immunity test: , 3, conforming to IEC 61000-4-4 Immunity to radiated fields: (26...1000 MHz), 10 V/m, conforming to IEC 61000-4-3 Radiated radio-frequency electromagnetic field immunity test: (0.15...80 MHz), 10 V, conforming to IEC 61000-4-6 Surge immunity test: (8...20 µs in differential mode), 0.6 kV, conforming to IEC 61000-4-5 Surge immunity test: (1.2...50 µs in common mode), 2 kV, conforming to IEC 61000-4-5","[Ui] rated insulation voltage":"750 V","[Ue] rated operational voltage":"690 V","Ambient air temperature for storage":"-40...70 °C","Ambient air temperature for operation":"-5...40 °C wall mounted -5...60 °C floor mounting","[Ics] rated service breaking capacity":"50 kA at 415 V conforming to IEC 60439-1","[Uimp] rated impulse withstand voltage":"6 kV for power circuit","[Icw] rated short-time withstand current":"9.1 kA for 70 ms conforming to IEC 60439-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$276.03","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/vn/en/product/LAD9AP3D1/tesys-d-lad9-control-connection-module-for-direct-motor-starter-gv2megv3p/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LAD9AP3D1/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for LAD9AP3D1?","answer":"Submit an RFQ through this listing."},{"question":"What standards does the LAD9AP3D1 comply with?","answer":"It is designed to IEC 60439-1 for low-voltage switchgear and controlgear assemblies, with pollution degree 3 and a rated short-time withstand current of 9.1 kA for 70 ms."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LAD9AP3D1","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LAD9AP3D1 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}