{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LADN13P","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LADN13P","canonicalUrl":"https://aoctrl.com/schneider/LADN13P","factsUrl":"https://aoctrl.com/api/mcp/products/LADN13P","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca LADN13P auxiliary contact block, 1 NO + 3 NC, front mounting, screw clamp terminals, IP20.","salesMarkdown":"It provides instantaneous contact operation for control-circuit feedback, interlocking, or status indication. The screw clamp terminals accept 1 to 2.5 mm² flexible or rigid wire, with a tightening torque of 1.7 N.m using a flat, Philips, or Pozidriv No. 2 screwdriver. Rated operational current (Ie) is 6 A at 120 V AC-15, which covers typical solenoid and contactor coil loads in control circuits. At 690 V AC-15 it drops to 1.04 A — the AC-15 category (IEC 60947-5-1) governs electromagnetic loads, so this is the rating that matters for switching contactor coils, not the higher thermal current. For DC control circuits, it handles 0.55 A at 125 V DC-13 and 0.1 A at 600 V DC-13. The conventional free-air thermal current (Ith) is 10 A at 60 °C, but that's a resistive-load benchmark — don't use it to size for inductive loads. Minimum switching capability is 5 mA at 17 V, so it can handle low-energy PLC-level signals without contact wetting issues. Rated insulation voltage (Ui) is 690 V per IEC 60947-5-1, and 600 V per UL/CSA. IP20 protection means it's suitable for enclosed panel mounting only — no washdown or dust-tight rating. Dimensions are 44 mm wide, 48 mm high, and 42 mm deep — it clips onto the front of a TeSys D or TeSys F contactor without adding DIN-rail width. The front-mount position means it occupies the space above the contactor's main poles, so check clearance above the contactor in the enclosure layout. Operating altitude is rated to 3000 m without derating. Protection against the external GG fuse is specified at 10 A — this is the maximum fuse rating for short-circuit protection on the control circuit feeding this block. Permissible short-time ratings: 100 A for 1 s, 120 A for 500 ms, 140 A for 100 ms at 60 °C, which covers inrush from multiple contactor coils. Making capacity is 140 A AC and 250 A DC per IEC 60947-5-1. Certified to EN/IEC 60947-5-1, GB/T 14048.5, EN 50012, UL 60947-5-1, CSA C22.2 No 60947-5-1, and meets glow-wire requirements of IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ for appliance applications. Protective treatment is TH per IEC 60068 for tropical environments. Insulation resistance exceeds 10 MOhm.","metaTitle":"Schneider Electric LADN13P TeSys Deca Auxiliary Contact Bloc","metaDescription":"Schneider Electric LADN13P TeSys Deca auxiliary contact block, 1NO+3NC, front mount, screw clamp terminals. Obsolete — sourced to order against RFQ. IEC/UL/CSA certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"42 mm","Width":"44 mm","Height":"48 mm","Current":"6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13","Voltage":"690 V AC 25...400 Hz","IP Rating":"IP20","Product Status":"Active","Protection Type":"GG fuse 10 A","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Temp Operating Max":"60 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-60...80 °C","Mechanical Life Cycles":"30 Mcycles","Main Product Or Component Type":"Auxiliary contact block","Ambient Air Temperature Operation":"-5...60 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/99c35f4aae632849f0d15d5c6d724a1b.pdf","sourceUrl":"https://www.se.com/nl/en/product/LADN13P/auxiliary-contact-block-tesys-deca-1no+3nc-front-mounting-screw-clamp-terminals-en-50012/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LADN13P/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LADN13P","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LADN13P when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}