{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LADT29","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LADT29","canonicalUrl":"https://aoctrl.com/schneider/LADT29","factsUrl":"https://aoctrl.com/api/mcp/products/LADT29","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys Deca time delay auxiliary contact block, LADT29, 1NO+1NC, on delay 1-30 s, front mount, Faston terminals.","salesMarkdown":"The LADT29: Rated operational current (Ie) is 6 A at 120 V AC-15, which covers typical solenoid and contactor coil loads in control circuits; at 690 V AC-15 it drops to 1.04 A, reflecting the reduced switching capacity at higher voltage. For DC-13 duty (solenoid loads), the rating is 0.55 A at 125 V DC and 0.1 A at 600 V DC — these are the values that govern fit for DC interposing relays or valve drivers, not the AC figures. The conventional free air thermal current (Ith) is 10 A at 60 °C, which sets the continuous current limit through the block irrespective of load type. Insulation voltage (Ui) is rated at 690 V per IEC 60947-5-1, and 600 V per UL/CSA — this establishes the voltage class for panel design and clearance requirements. The minimum switching capability of 5 mA at 17 V means the contacts will reliably switch low-level signals common in PLC inputs or pilot lights, but anything below those thresholds risks contact wetting failure. This block mounts on the front of a TeSys Deca contactor or reversing starter, adding a timed auxiliary function without increasing the panel depth beyond 61 mm.","metaTitle":"Schneider LADT29 TeSys Deca Time Delay Block, On Delay 1-30s","metaDescription":"LADT29 is obsolete. TeSys Deca on-delay auxiliary contact block, 1NO+1NC, 1-30s range, Faston terminals. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"61 mm","Width":"44 mm","Height":"48 mm","Current":"6 A at 120 V AC-15 1.04 A at 690 V AC-15 0.55 A at 125 V DC-13 0.1 A at 600 V DC-13","Voltage":"690 V AC 25...400 Hz","IP Rating":"IP20","Timer Type":"On delay","Product Status":"Active","Protection Type":"GG fuse 10 A","Temp Storage Max":"80 °C","Temp Storage Min":"-60 °C","Time Delay Range":"1–30 s","Temp Operating Max":"70 °C","Temp Operating Min":"-40 °C","Temperature Storage":"-60...80 °C","Mechanical Life Cycles":"5 Mcycles","Ambient Air Temperature Operation":"-40...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/631d13e137d8009c8f3df41565e76fe4.pdf","sourceUrl":"https://www.se.com/uk/en/product/LADT29/time-delay-auxiliary-contact-block-tesys-deca-1no-+-1nc-on-delay-130s-front-faston-terminals/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LADT29/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LADT29","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LADT29 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}