{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LAERCU","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LAERCU","canonicalUrl":"https://aoctrl.com/schneider/LAERCU","factsUrl":"https://aoctrl.com/api/mcp/products/LAERCU","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, suppressor module LAERCU, RC circuit, 110-240 V AC 50/60 Hz, clip-on front mount, IP20.","salesMarkdown":"It uses an RC circuit (resistor-capacitor snubber) rated for a control circuit voltage of 110...240 V AC 50/60 Hz, with a maximum peak voltage of 3 Uc at up to 400 Hz. This means it absorbs the inductive kick when the coil de-energizes, protecting nearby electronics and extending contact life. The module clips onto the front of an Easy TeSys contactor or reversing starter, occupying 44 mm width and 33 mm depth. No tools needed for installation — it snaps into a dedicated slot. The IP20 finger-safe housing (conforming to IEC 60529) allows panel integration without additional shrouding in a standard enclosure. Protective treatment per TH (IEC 60068) means it handles humid or mildly corrosive atmospheres typical in HVAC or pump panels. ## Sourcing reality The 110-240 V AC coil voltage and Easy TeSys form factor confirm fit for the BOM line.","metaTitle":"Schneider LAERCU Easy TeSys Suppressor Module, RC Circuit, 1","metaDescription":"LAERCU suppressor module for Easy TeSys Control. RC circuit, 110-240 V AC 50/60 Hz, clip-on front mount, IP20. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"33 mm","Range":"Easy TeSys","Width":"44 mm","title":"LAERCU","Standards":"IEC 60947-5-1","description":"Suppressor module,Easy TeSys Control,RC circuit,110-240 V","Mounting mode":"Clip-on","lifecycle_stage":"current","Range of product":"Easy TeSys Control","Device short name":"LAERC","Mounting location":"Front","Maximum peak voltage":"3 Uc <= 400 Hz","Protective treatment":"TH conforming to IEC 60068","Suppressor technology":"RC circuit","IP degree of protection":"IP20 conforming to IEC 60529","Product or component type":"Suppressor module","[Uc] control circuit voltage":"110...240 V AC 50/60 Hz","Ambient air temperature for storage":"-60...80 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$9.45","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f657bbc30e4062a331a556021cef8051.pdf","sourceUrl":"https://www.se.com/id/en/product/LAERCU/suppressor-moduleeasy-tesys-controlrc-circuit110240-v/"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"The module is 44 mm wide and 33 mm deep, clipping onto the front of the contactor — it does not add to the contactor's depth beyond that."},{"question":"What compliance documentation is available?","answer":"The module is designed to IEC 60947-5-1 and carries IP20 protection per IEC 60529. Protective treatment conforms to TH per IEC 60068. For specific RoHS/REACH/UL declarations, the manufacturer's documentation portal is the source."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LAERCU","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LAERCU when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}