{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1D400086E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1D400086E7","canonicalUrl":"https://aoctrl.com/schneider/LC1D400086E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1D400086E7","rawCanonicalId":null},"summary":{"shortDescription":"TeSys Deca contactor, 4P(2 NO + 2 NC), AC-1 <= 440V, 60 A, 48V AC 50/60 Hz coil","salesMarkdown":null,"metaTitle":null,"metaDescription":null,"metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"125 mm","Range":"TeSys","Width":"85 mm","Height":"127 mm","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508","Operating time":"4...19 ms opening 12...26 ms closing","Coil technology":"Without built-in suppressor module","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"mature","Flame retardance":"V1 conforming to UL 94","Heat dissipation":"4...5 W at 50/60 Hz","Mounting support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of product":"TeSys Deca","Average impedance":"1.5 mOhm - Ith 60 A 50 Hz for power circuit","Device short name":"LC1D","Poles description":"4P","Tightening torque":"Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5 Control circuit: 1.7 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5 Power circuit: 2.5 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6","Climatic withstand":"conforming to IACS E10 exposure to damp heat","Compatibility code":"LC1D","Inrush power in VA":"140 VA 60 Hz cos phi 0.75 (at 20 °C) 160 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"0...3000 m","Control circuit type":"AC at 50/60 Hz","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"1.4 Mcycles 60 A AC-1 at Ue <= 440 V","Mechanical durability":"6 Mcycles","Mechanical robustness":"Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz)","Associated fuse rating":"80 A gG at 80 A gG at <= 690 V coordination type 2 for power circuit","Connections - terminals":"Control circuit: lugs-ring terminals - external diameter: 8 mm Power circuit: lugs-ring terminals - external diameter: 16.5 mm","IP degree of protection":"IP20 front face conforming to IEC 60529","Rated breaking capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1","Product or component type":"Contactor","Irms rated making capacity":"800 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"5.4 W AC-1","[Uc] control circuit voltage":"48 V AC 50/60 Hz","[Ui] rated insulation voltage":"Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-40...70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40...60 °C):operational AC 60 Hz 1...1.1 Uc (60...70 °C):operational AC 50/60 Hz","[Ie] rated operational current":"60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: Power circuit: <= 300 V DC","Hold-in power consumption in VA":"13 VA 60 Hz cos phi 0.3 (at 20 °C) 15 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"320 A 40 °C - 10 s for power circuit 720 A 40 °C - 1 s for power circuit 72 A 40 °C - 10 min for power circuit 165 A 40 °C - 1 min for power circuit","[Ith] conventional free air thermal current":"60 A (at 60 °C) for power circuit","Permissible ambient air temperature around the device":"-40...60 °C 60...70 °C with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/76e26d7d42ebc787d8892af451aa3127.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1D400086E7/tesys-deca-contactor-4p2-no-+-2-nc-ac1-440v-60-a-48v-ac-50-60-hz-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1D400086E7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1D400086E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1D400086E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}