{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1D40G7M","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1D40G7M","canonicalUrl":"https://aoctrl.com/schneider/LC1D40G7M","factsUrl":"https://aoctrl.com/api/mcp/products/LC1D40G7M","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric TeSys D LC1D40G7M, IEC contactor, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3-phase, 3 NO, 120VAC 50/60Hz coil, open style.","salesMarkdown":"The Schneider Electric TeSys D LC1D40G7M is a 40A IEC contactor rated for motor control and resistive loads, with a 120VAC 50/60Hz coil. Rated for AC-1 (resistive), AC-3 (squirrel-cage motor starting/running), AC-4 (plugging/inching), and AC-3e (enhanced motor) utilisation categories, so it covers both standard and high-stress motor applications. The 3-pole, 3 NO configuration is the typical motor-switching layout. Certified to CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 60947-4-1 — these cover the contactor's performance and safety for industrial control panels. Fire resistance rated to 1562 °F (850 °C) per IEC 60695-2-1, and flame retardance V1 per UL 94. Operates at altitudes up to 9842 ft (3000 m) without derating. Ambient temperature range -40 to 140 °F (-40 to 60 °C), with derating up to 158 °F (70 °C) — suitable for most control cabinets. Mounts on plate or rail (DIN), and the open-style frame fits standard panel layouts. Dimensions: 5 in height, 3 in width, 4.7 in depth. Mechanical robustness: withstands vibrations of 2 Gn (open) and 3 Gn (closed) at 5-300 Hz, and shocks of 8 Gn (open) and 10 Gn (closed) for 11 ms — field-service techs can expect it to hold up in moderate-vibration environments like pump skids or conveyor drives.","metaTitle":"Schneider LC1D40G7M TeSys D Contactor, 40A, 120VAC Coil","metaDescription":"Schneider Electric TeSys D LC1D40G7M IEC contactor, 40A, 30HP at 480VAC, 3-pole, 120VAC 50/60Hz coil. Active production. UL/CSA/IEC certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"4.7 in (119 mm)","Range":"TeSys","Width":"3.0 in (75 mm)","title":"LC1D40G7M","Height":"5 in (127 mm)","Category":"US10I1222357","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","description":"IEC contactor, TeSys D, nonreversing, 40A, 30HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 120VAC 50/60Hz coil, open","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"mature","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Non-overlap time":"1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact","Range of Product":"TeSys Deca","Device short name":"LC1D","Poles description":"3P","Climatic withstand":"IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat","Operating altitude":"0...9842.52 ft (0...3000 m)","Utilisation category":"AC-1 AC-4 AC-3 AC-3e","Contactor application":"Resistive load Motor control","Mechanical robustness":"Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms)","Nbr. of units in pkg.":"1","Product or Component Type":"Contactor","[Ue] rated operational voltage":"Power circuit 10 MOhm for signalling circuit","Permissible ambient air temperature around the device":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$357.59","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1781627843f638706b1c98ec71e9b25e.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1D40G7M/iec-contactor-tesys-d-nonreversing-40a-30hp-at-480vac-up-to-100ka-sccr-3-phase-3-no-120vac-50-60hz-coil-open/"},"ai":{"faq":[{"question":"What are the key ratings for the LC1D40G7M?","answer":"It's a 40A IEC contactor rated for 30HP at 480VAC, with a 120VAC 50/60Hz coil. Supports AC-1, AC-3, AC-4, and AC-3e utilisation categories, and SCCR up to 100kA. Three-pole, three normally open contacts."},{"question":"What compliance documentation does Schneider provide for the LC1D40G7M?","answer":"The contactor is certified to CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, and UL 60947-4-1. Fire resistance per IEC 60695-2-1 at 1562 °F (850 °C), and flame retardance V1 per UL 94."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1D40G7M","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1D40G7M when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}