{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1D50G7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1D50G7","canonicalUrl":"https://aoctrl.com/schneider/LC1D50G7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1D50G7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider LC1D50G7 Iec Contactors 38 65 Amp — now discontinued, supplied from remaining surplus and broker stock.","salesMarkdown":"## Overview The LC1D50G7 is a Schneider TeSys Deca IEC contactor rated for 50 A continuous current across 3 poles, energized by a 120 V AC 60 Hz coil. It handles motor and resistive loads under AC-1 through AC-4 utilization categories, with a maximum rated voltage of 600 V AC. The contactor carries UL 60947-4-1, IEC 60947-4-1, and CSA C22.2 No. 14 listings, plus California Proposition 65 compliance, meeting typical panel documentation requirements.","metaTitle":"Schneider LC1D50G7 TeSys Deca contactor, 50 A, 120 V AC coil","metaDescription":"Schneider LC1D50G7 TeSys Deca IEC contactor: 50 A rated current, 3-pole, 120 V AC coil, 600 V AC max, UL/CSA/IEC listed. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"4.7 in (119 mm)","Range":"TeSys","Width":"2.2 in (55 mm)","Height":"4.8 in (122 mm)","Category":"US10I1222357","Standards":"UL 60947-4-1 EN 60947-4-1 EN 60947-5-1 IEC 60947-5-1 CSA C22.2 No 14 IEC 60947-4-1","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"mature","Flame retardance":"V1 conforming to UL 94","Mounting Support":"Plate Rail","Non-overlap time":"1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts","Range of Product":"TeSys Deca","Device short name":"LC1D","Poles description":"3P","Climatic withstand":"IACS E10 exposure to damp heat","Operating altitude":"9842.52 ft (3000 m) without derating","Utilisation category":"AC-3 AC-2 AC-4 AC-1 AC-3e","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor opened 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz)","Nbr. of units in pkg.":"1","IP degree of protection":"IP2X IEC 60529 IP2X VDE 0106","Product or Component Type":"Contactor","[Ue] rated operational voltage":"Power circuit 10 MOhm for control circuit","Permissible ambient air temperature around the device":"23...140 °F (-5...60 °C) -40...158 °F (-40...70 °C) at Uc"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$396.00 – $477.37","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7b53340ca6d093ddb700f0fb3a433b3f.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1D50G7/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1D50G7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1D50G7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}