{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1D65008D7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1D65008D7","canonicalUrl":"https://aoctrl.com/schneider/LC1D65008D7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1D65008D7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, TeSys Deca, 4-pole contactor, LC1D65008D7, 80 A AC-1, 4.9 in depth.","salesMarkdown":"## Part overview It carries an 80 A continuous rating at 440 V and is offered with an AC 50/60 Hz coil without an integral suppressor module — plan for an external RC snubber or diode if driving inductive loads. Compliance with IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No 14 means the contactor meets installation codes across North America and Europe. The coil inrush at 50 Hz is 160 VA (cos φ 0.75), settling to a holding dissipation of 4–5 W. Electrical durability is specified at 1.4 million cycles at 80 A AC-1 (≤ 440 V), with mechanical endurance rated at 6 million cycles — figures that align with a general-purpose switching component for moderate-duty applications. Given the mature lifecycle, expect consistent lead times and no forced replacement risk in the near term. If a newer-generation TeSys Giga equivalent is under evaluation, the physical footprint and mounting pattern differ — verify panel layout before substituting. The LC1D65008D7 accepts screw-clamp terminals on both power and control circuits. Power conductors up to 35 mm² flexible (with or without ferrule) are accommodated; the control circuit accepts 1–4 mm². Torque settings: power circuit 8 N·m for hexagonal drive (4 mm), control circuit 1.7 N·m (flat Ø 6 mm or Pozidriv No 2). Mounting options include plate or rail (35 mm DIN rail). The 4-pole footprint measures 85 mm wide × 127 mm tall × 125 mm deep — factor this into gland-plate clearance, especially for through-panel wiring. IP20 rated on the front face. Associated fuse recommendation for type 2 coordination on the power circuit is 125 A gG at ≤ 690 V. No protective cover is supplied; if finger-safe termination is required, order a separate shrouding kit from the TeSys Deca accessories family.","metaTitle":"Schneider LC1D65008D7 4-Pole TeSys Deca Contactor 80A","metaDescription":"Mature lifecycle 4-pole contactor rated 80A AC-1 resistive load 440V. IEC/UL/CSA approved. Sourced to order. Depth 4.9 in.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"4.9 in (125 mm)","Range":"TeSys","Width":"3.3 in (85 mm)","Height":"5 in (127 mm)","Category":"US10I1222357","Standards":"CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1","Operating time":"4...19 ms opening 12...26 ms closing","Coil technology":"Without built-in suppressor module","Fire resistance":"1562 °F (850 °C) IEC 60695-2-1","lifecycle_stage":"mature","Flame retardance":"V1 conforming to UL 94","Heat dissipation":"4...5 W at 50/60 Hz","Mounting Support":"Plate Rail","Pollution degree":"3","Protective cover":"Without","Range of Product":"TeSys Deca","Average impedance":"1.5 mOhm - Ith 80 A 50 Hz for power circuit","Device short name":"LC1D","Poles description":"4P","Tightening torque":"Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2 Power circuit 70.8 lbf.in (8 N.m) screw clamp terminals 0.04...0.05 in² (25...35 mm²) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) screw clamp terminals 0.002...0.04 in² (1...25 mm²) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2","Climatic withstand":"IACS E10 exposure to damp heat","Compatibility code":"LC1D","Inrush power in VA":"140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))","Operating altitude":"0...9842.52 ft (0...3000 m)","Control circuit type":"AC 50/60 Hz","Overvoltage category":"III","Protective treatment":"THIEC 60068-2-30","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"1.4 Mcycles 80 A AC-1 <= 440 V","Mechanical durability":"6 Mcycles","Mechanical robustness":"Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 3 Gn, 5...300 Hz)","Nbr. of units in pkg.":"1","Associated fuse rating":"125 A gG at 125 A gG at <= 690 V coordination type 2 for power circuit","Maximum operating rate":"3600 cyc/h at 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 0.002...0.05 in² (1...35 mm²) - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 0.002...0.04 in² (1...25 mm²) - cable stiffness: solid without cable end","IP degree of protection":"IP20 front face IEC 60529","Rated breaking capacity":"1000 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Safety reliability level":"B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1","Product or Component Type":"Contactor","Irms rated making capacity":"1000 A at 440 V for power circuit conforming to IEC 60947","Power dissipation per pole":"9.6 W AC-1","[Uc] control circuit voltage":"42 V AC 50/60 Hz","[Ui] rated insulation voltage":"Power circuit 600 V CSA Power circuit 600 V UL Power circuit 690 V IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 50 Hz 0.85...1.1 Uc (-40...140 °F (-40...60 °C)):operational AC 60 Hz 1...1.1 Uc (140...158 °F (60...70 °C)):operational AC 50/60 Hz","[Ie] rated operational current":"80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit Power circuit <= 300 V DC","Hold-in power consumption in VA":"13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))","[Uimp] rated impulse withstand voltage":"6 kV IEC 60947","[Icw] rated short-time withstand current":"640 A 104 °F (40 °C) - 10 s for power circuit 900 A 104 °F (40 °C) - 1 s for power circuit 110 A 104 °F (40 °C) - 10 min for power circuit 260 A 104 °F (40 °C) - 1 min for power circuit","[Ith] conventional free air thermal current":"80 A (at 140 °F (60 °C)) for power circuit","Permissible ambient air temperature around the device":"-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$765.00","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3918f8b4dc502b538f9a0e99b26bc376.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1D65008D7/alternatives.json"},"ai":{"faq":[{"question":"What are the key electrical ratings of this contactor?","answer":"The contactor is rated 80 A in AC-1 utilisation category (resistive load) at ≤ 440 V. It is a 4-pole device with an AC 50/60 Hz coil. Inrush at 50 Hz is 160 VA; hold power dissipation is 4–5 W."},{"question":"What compliance certifications does the LC1D65008D7 hold?","answer":"It complies with IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, and CSA C22.2 No 14, covering installations in North America and international markets."},{"question":"How is the LC1D65008D7 sourced?","answer":"This contactor is sourced to order via RFQ. Given its mature lifecycle status, lead times are generally stable. Contact our sales desk for current pricing and availability."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1D65008D7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1D65008D7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}