{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E06004M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E06004M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E06004M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E06004M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, contactor LC1E06004M5WBIN, 4 NO poles, 20 A AC-1 at ≤415 V, 220 V AC 50 Hz coil, screw clamp terminals, IP20.","salesMarkdown":"The LC1E06004M5WBIN: AC-1 is the resistive-load curve — this contactor is not rated for motor starting (AC-3) or inductive switching. The 20 A rating at ≤415 V is the operational current for that duty; the rated breaking capacity is 48 A at 440 V, and the making capacity hits 60 A at 440 V AC per IEC 60947-4-1. Electrical durability is 150,000 cycles under AC-1, with mechanical durability at 10 million cycles — a solid figure for a panel that cycles a few times per hour. The 4 NO pole configuration with no auxiliary contacts means you'll need a separate contactor or relay block for feedback signals. Control circuit screw-clamp terminals accept 1 to 4 mm² flexible with cable end, or up to 6 mm² solid. The 80 mm depth, 45 mm width, and 74 mm height fit standard DIN-rail or plate mounting — no surprises for panel layout. Protective treatment TH per IEC 60068 means it's tested for tropical humidity — no extra coating needed for damp environments. Active lifecycle status means it's a current catalog item, not a phase-out. ## Sourcing and integration The 12 A gG fuse coordination type 1 at ≤690 V is specified for the power circuit; use that as the upstream protection limit.","metaTitle":"Schneider LC1E06004M5WBIN Easy TeSys Contactor, 20 A AC-1, 2","metaDescription":"Schneider Electric LC1E06004M5WBIN Easy TeSys 4-pole contactor, 20 A AC-1 at 415 V, 220 V AC 50 Hz coil. Active production. Sourced to order. Depth 80 mm.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 20 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"150000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"12 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"48 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"60 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"1 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"20 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"80 A 40 °C - 10 s for power circuit 45 A 40 °C - 60 s for power circuit 20 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"20 A (at 40 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E06004M5WBIN/easy-tesys-contactor-4p-ctr-32a-ac14no220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E06004M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current 20 A in AC-1 at ≤415 V, control circuit voltage 220 V AC 50 Hz, 4 NO poles, rated insulation voltage 690 V, and electrical durability 150,000 cycles under AC-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E06004M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E06004M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}