{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E06008M5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E06008M5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E06008M5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E06008M5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E06008M5WB, 4-pole, 16 A AC-1 rated operational current, 220 V AC 50 Hz coil, screw clamp terminals, IP20.","salesMarkdown":"Its rated operational current is 16 A at ≤ 440 V AC in utilisation category AC-1, which means it is sized for resistive heating, lighting, or transformer loads — not motor starting, where the AC-3 rating would govern. The coil is a 220 V AC 50 Hz wide-range type, with a drop-out threshold of 0.3 to 0.6 Uc and an operational range of 0.7 to 1.25 Uc across -5 to 55 °C. The pole contact composition is 2 normally open and 2 normally closed, with no auxiliary contact block included. ## Integration notes The contactor occupies 45 mm width on a DIN rail or plate mount, with a depth of 80 mm and height of 74 mm. Power and control circuit connections use screw clamp terminals accepting 1 to 4 mm² flexible or solid wire. Tightening torque is 1.2 N.m for both power and control circuits. The heat dissipation is 2 to 3 W for the control circuit and 1 W per pole in AC-1 duty, so panel thermal calculations should account for roughly 7 W total at full load. The associated fuse rating is 12 A gG at ≤ 690 V for coordination type 1. Electrical durability is 150,000 cycles in AC-1 duty. The contactor operates without derating up to 3000 m altitude.","metaTitle":"Schneider Electric LC1E06008M5WB Easy TeSys Contactor, 16 A","metaDescription":"Schneider Electric LC1E06008M5WB Easy TeSys Control contactor. 16 A rated operational current AC-1, 220 V AC 50 Hz coil, 4-pole 2 NO + 2 NC. Current lifecycle stage. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 16 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"150000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"12 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"48 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"60 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"1 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"16 A (at <55 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.3 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"80 A 40 °C - 10 s for power circuit 45 A 40 °C - 60 s for power circuit 20 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"16 A (at 55 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ea81426d615a2dd2c6449c47400f0c00.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E06008M5WB/easypact-tvs-contactor-4p-ctr-16a-ac12no+2nc220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E06008M5WB/alternatives.json"},"ai":{"faq":[{"question":"What is the rated operational current of the LC1E06008M5WB?","answer":"The rated operational current is 16 A at ≤ 440 V AC in utilisation category AC-1 (resistive load). This is the current it can carry continuously when switching resistive loads."},{"question":"What is the control voltage for this contactor?","answer":"The control circuit voltage is 220 V AC at 50 Hz. It is a wide-range coil that operates between 0.7 and 1.25 Uc and drops out between 0.3 and 0.6 Uc across -5 to 55 °C."},{"question":"What compliance documentation is available for the LC1E06008M5WB?","answer":"The contactor is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the equivalent GB/T standards. It also carries TH protective treatment per IEC 60068-2-30 and fire resistance per IEC 60695-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E06008M5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E06008M5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}