{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E06008N5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E06008N5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E06008N5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E06008N5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E06008N5WB, 4-pole contactor, 16 A rated operational current AC-1, 415 V AC 50 Hz coil, DIN rail or plate mount.","salesMarkdown":"The 415 V AC 50 Hz coil is a wide-range AC control circuit, with a drop-out threshold of 0.3 to 0.6 Uc and an operational range of 0.7 to 1.25 Uc across -5 to 55 °C, so it holds in reliably on a nominal 415 V line and drops cleanly on undervoltage. The 4-pole arrangement (2 NO + 2 NC) gives flexibility for switching two independent resistive loads or combining a load with a signalling contact — no auxiliary contact block needed for basic feedback. Screw-clamp terminals on both power and control circuits accept flexible wire with or without ferrules (1 to 4 mm²) and solid wire up to 4 mm²; tightening torque is 1.2 N.m for both circuits, so one driver setting covers the whole install.","metaTitle":"Schneider Electric LC1E06008N5WB Easy TeSys Contactor, 16 A","metaDescription":"Schneider Electric LC1E06008N5WB Easy TeSys contactor, 16 A rated operational current at 440 V AC-1, 4-pole (2 NO + 2 NC), 415 V AC 50 Hz coil. Current lifecycle stage. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 16 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m without derating","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068-2-30","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"150000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"12 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"48 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"60 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"1 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"16 A (at <55 °C) at <= 440 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.3 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"80 A 40 °C - 10 s for power circuit 45 A 40 °C - 60 s for power circuit 20 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"16 A (at 55 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/62be3c3d5e335e3b82273dca96dca2bb.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E06008N5WB/contactoreasy-tesys-controllc1e4p2no+2ncac1-16a415v50hz-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E06008N5WB/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LC1E06008N5WB?","answer":"Rated operational current is 16 A at ≤440 V AC under AC-1 (resistive load). Control coil is 415 V AC 50 Hz. The contactor is 4-pole with 2 NO + 2 NC main contacts and no auxiliary contact block. Insulation voltage is 690 V, and the rated breaking capacity is 48 A at 440 V."},{"question":"What compliance standards does the LC1E06008N5WB meet?","answer":"It is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents. Fire resistance is 850 °C per IEC 60695-2-1. The protective treatment is TH conforming to IEC 60068-2-30, and the IP degree of protection is IP20."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E06008N5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E06008N5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}