{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E0610Q6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E0610Q6","canonicalUrl":"https://aoctrl.com/schneider/LC1E0610Q6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E0610Q6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, contactor, LC1E0610Q6, 3P (3NO), AC-3/AC-3e ≤440V 6A, 380V AC coil 60Hz, 1NO auxiliary contact, DIN rail/plate mount.","salesMarkdown":"The Schneider Electric LC1E0610Q6 is a 3-pole contactor from the Easy TeSys Control range, rated for AC-3/AC-3e motor switching up to 6 A at ≤440 V, with a 380 V AC 60 Hz coil and one normally-open auxiliary contact. The AC-3 rating of 6 A at ≤440 V defines its motor-switching capability — this is the current it can make and break under full-load motor starting conditions. The 380 V AC coil at 60 Hz matches North American or 60 Hz supply systems; verify your control voltage matches exactly. The 1.5 ms non-overlap time between NC and NO contacts ensures safe break-before-make in reversing or interlocking circuits. ## Integration notes Dimensions are 45 mm wide, 74 mm high, 80 mm deep — fits standard panel cutouts. The 380 V AC coil draws its rated power from the control circuit; ensure the control transformer or PLC output can supply the inrush. The 1NO auxiliary contact can be used for status feedback or interlocking.","metaTitle":"Schneider LC1E0610Q6 Easy TeSys Contactor, 3P, AC-3 6A, 380V","metaDescription":"Obsolete Schneider LC1E0610Q6 Easy TeSys contactor, 3P, AC-3 6A, 380V AC 60Hz coil, 1NO aux. Sourced to order against RFQ. DIN rail mount, EN/IEC 60947 compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/088d40dfe5f6aa967d847c3a88e89030.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1E0610Q6/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v6a380v-ac-coil60hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E0610Q6/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1E0610Q6?","answer":"It is a 3-pole contactor rated AC-3/AC-3e at 6 A, ≤440 V, with a 380 V AC 60 Hz coil and one normally-open auxiliary contact. It mounts on a DIN rail or plate and complies with EN/IEC 60947 series standards."},{"question":"What compliance documentation does Schneider provide for this part?","answer":"The contactor is certified to EN/IEC 60947-1, -4-1, -5-1, and GB/T 14048 equivalents. It also meets fire resistance at 850 °C per IEC 60695-2-1 and protective treatment TH (pollution degree 3) per IEC 60068-2-30."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E0610Q6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E0610Q6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}