{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E09004N5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E09004N5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E09004N5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E09004N5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, 4-pole 4 NO, 25 A AC-1 at ≤415 V, 415 V AC 50 Hz coil, screw clamp terminals, IP20, DIN rail/plate mount.","salesMarkdown":"Its 25 A rated operational current at ≤415 V AC (at <40 °C) means it handles heater banks, lighting, or other non-inductive loads up to that current — not motor starting, which would need an AC-3 rated contactor. The 415 V AC 50 Hz coil is wide-range, so it pulls in reliably between 0.7 and 1.25 times Uc and drops out between 0.3 and 0.6 times Uc across -5 to 55 °C. With 4 normally-open poles and no auxiliary contacts built in, this contactor is a straight power-switching device — you add a separate auxiliary block if you need feedback or interlocking. The screw-clamp terminals accept up to 6 mm² solid or 4 mm² flexible with ferrules, tightened to 1.2 N.m on both power and control circuits. Operating altitude up to 3000 m covers most sites without derating. The 25 A AC-1 rating is the headline number, but the breaking capacity tells you more about fault handling: 72 A at 440 V per IEC 60947, and a making capacity of 90 A at 440 V AC. That's the contactor's ability to close onto and interrupt a fault — not something you'd design for, but it confirms the part can survive a downstream short without welding shut, provided the upstream fuse (12 A gG at ≤690 V, coordination type 1) clears the fault. Electrical durability is 150,000 cycles at AC-1 — that's the resistive-load life. Mechanical durability is 10 million cycles, so in a low-current signalling application it'll outlast the panel. The 1.6 W dissipation per pole at AC-1 means the total heat load inside the enclosure is about 6.4 W for all four poles, plus 2 to 3 W from the coil — negligible for most cabinets.","metaTitle":"Schneider Electric LC1E09004N5WBIN Easy TeSys Contactor, 25","metaDescription":"Schneider Electric LC1E09004N5WBIN Easy TeSys Control contactor. 25 A rated operational current AC-1 at ≤415 V, 4-pole 4 NO, 415 V AC 50 Hz coil. Active production, sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 25 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"150000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"12 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"72 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"90 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"1.6 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"25 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"105 A 40 °C - 10 s for power circuit 61 A 40 °C - 60 s for power circuit 30 A 40 °C - 600 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E09004N5WBIN/easy-tesys-contactor-4p-ctr-40a-ac14no415v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E09004N5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"Rated operational current is 25 A at ≤415 V AC under AC-1 (resistive load). The coil is 415 V AC 50 Hz wide-range. It has 4 normally-open poles, no auxiliary contacts, and an IP20 enclosure. Electrical durability is 150,000 cycles AC-1; mechanical durability is 10 million cycles."},{"question":"What compliance standards does it meet?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents. It carries a TH protective treatment per IEC 60068 for tropical environments and is rated for 850 °C fire resistance per IEC 60695-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E09004N5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E09004N5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}