{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E09004N7IN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E09004N7IN","canonicalUrl":"https://aoctrl.com/schneider/LC1E09004N7IN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E09004N7IN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control LC1E09004N7IN, 4P(4NO) contactor, AC-1 ≤415V 25A at 415V, DIN rail/plate mount, obsolete.","salesMarkdown":"It is rated for AC-1 utilisation category at 25 A up to 415 V, meaning it is designed for switching resistive loads — heaters, lighting banks, or other non-inductive circuits — in control panels. The IP2X degree of protection means the enclosure resists finger contact but is not sealed against dust or moisture — it belongs inside a cabinet, not on a washdown line. The 25 A AC-1 rating is the headline number, but note the duty: AC-1 is resistive load. If your circuit drives motors, transformers, or other inductive loads, the contactor's AC-3 or AC-4 rating would be lower — this part does not carry those categories in its listing. The 4NO pole configuration is fixed; there is no changeover (NC) pole on this variant. The non-overlap time of 1.5 ms on both energisation and de-energisation, guaranteed between NC and NO contacts, is a safety-relevant parameter for interlocking circuits where a make-before-break condition must be avoided. The protective treatment TH (pollution degree 3) per IEC 60068 means the contactor is treated for tropical humidity and moderate industrial atmospheres — condensation and conductive dust are expected in the environment, and the part is designed to withstand them without conformal coating.","metaTitle":"Schneider Electric LC1E09004N7IN Easy TeSys Contactor, 4P 25","metaDescription":"Obsolete Schneider Electric LC1E09004N7IN Easy TeSys Control 4-pole contactor. 25A AC-1 at 415V, 4NO, DIN rail mount. Sourced to order against RFQ via independent supply channels.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"4P","Operating altitude":"3000 m","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d61f9afdea877f2aac48b458d71e626d.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E09004N7IN/contactoreasy-tesys-controllc1e4p4noac1415v25a415v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E09004N7IN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a 4-pole, 4NO contactor rated 25 A in AC-1 (resistive load) at up to 415 V. Mounting is DIN rail or plate, with a 45 mm width. It complies with EN/IEC 60947-1, -4-1, -5-1 and the corresponding GB/T standards."},{"question":"What compliance documentation is available for this part?","answer":"The contactor carries approvals to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents GB/T 14048.1, GB/T 14048.4, GB/T 14048.5. Fire resistance is rated at 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E09004N7IN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E09004N7IN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}