{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E09004P7IN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E09004P7IN","canonicalUrl":"https://aoctrl.com/schneider/LC1E09004P7IN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E09004P7IN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E09004P7IN, 4-pole contactor, 4NO, AC-1 25A at ≤415V, 230V coil, DIN rail mount.","salesMarkdown":"It is rated for AC-1 utilisation category at 25 A, with a rated operational voltage up to 415 V and a 230 V coil. This makes it suited for switching resistive loads — heaters, lighting banks, or other non-inductive circuits — where the current is in phase with voltage and there is no motor inrush or inductive kick. AC-1 is a lower-stress duty than AC-3 (motor starting), so if your application involves motor loads, this contactor is not the right fit — you would need a part rated in AC-3. The 4NO pole configuration gives four independent switching paths, all closing together on coil energisation. Dimensions are 45 mm width, 74 mm height, and 80 mm depth. These are the core standards for low-voltage switchgear and controlgear — part 4-1 covers contactors and motor-starters, part 5-1 covers control-circuit devices. Operating altitude is rated to 3000 m without derating.","metaTitle":"Schneider Electric LC1E09004P7IN Easy TeSys Contactor, 4NO,","metaDescription":"Obsolete LC1E09004P7IN contactor from Schneider Electric Easy TeSys Control range. 4-pole 4NO, AC-1 rated 25A at ≤415V, 230V coil. Sourced to order against RFQ. EN/IEC 60947 compli","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"4P","Operating altitude":"3000 m","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/23f57e79c031e3050ae0dabfb3ab1e5f.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E09004P7IN/contactoreasy-tesys-controllc1e4p4noac1415v25a230v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E09004P7IN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a 4-pole 4NO contactor rated AC-1 at 25 A with a 230 V coil. The rated operational voltage is up to 415 V. It mounts on DIN rail and measures 45 x 74 x 80 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E09004P7IN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E09004P7IN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}