{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E0901F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E0901F7","canonicalUrl":"https://aoctrl.com/schneider/LC1E0901F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E0901F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E0901F7, 3P (3NO) contactor, AC-3/AC-3e ≤440V 9A, 110V AC 50/60Hz coil, 1NC auxiliary contact, DIN-rail/plate mount.","salesMarkdown":"The Schneider Electric LC1E0901F7 is a three-pole (3NO) contactor from the Easy TeSys Control range, rated for AC-3 and AC-3e duty at ≤440 V, 9 A — that's the motor-switching rating, so it handles a 4 kW (approx. 5.5 HP) induction motor on a 400 V line. The 110 V AC coil at 50/60 Hz pulls in reliably across the -5 to +55 °C operating ambient range. One normally-closed auxiliary contact is built in for feedback or interlock wiring. The IP2X finger-safe front keeps accidental contact out during commissioning. TH protective treatment per IEC 60068-2-30 means it survives humidity cycling (pollution degree 3) — a solid fit for a mill electrical room or a washdown-adjacent cabinet. Rated for 3000 m operating altitude without derating — no need to oversize for high-altitude sites. Vibration tolerance: 1.5 Gn open, 3 Gn closed across 5–300 Hz. Shock survival: 7 Gn open, 10 Gn closed (11 ms half-sine).","metaTitle":"Schneider Electric LC1E0901F7 Easy TeSys Contactor, 3P, 9A,","metaDescription":"Schneider Electric LC1E0901F7 Easy TeSys Control contactor. 3P (3NO), AC-3/AC-3e ≤440V 9A, 110V AC 50/60Hz coil, 1NC aux. Active production. DIN-rail/plate mount. EN/IEC 60947 comp","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1ab4441ce6f5f10bac26cd53e8358948.pdf","sourceUrl":"https://www.se.com/hk/en/product/LC1E0901F7/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v9a110v-ac-coil50-60hz1nc-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E0901F7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1E0901F7?","answer":"Three-pole (3NO), AC-3/AC-3e rated at 9 A, ≤440 V, with a 110 V AC 50/60 Hz coil. One NC auxiliary contact is included. Mounts on DIN rail or plate."},{"question":"What standards does the LC1E0901F7 comply with?","answer":"It meets EN/IEC 60947-1, -4-1, -5-1 and the corresponding GB/T 14048 series, plus IEC 60335-1 Clause 30.2 and IEC 60335-2-40 Annex JJ for appliance applications. Fire resistance tested at 850 °C per IEC 60695-2-1."},{"question":"Can the LC1E0901F7 be used in humid or corrosive environments?","answer":"Yes, it carries TH protective treatment (pollution degree 3) per IEC 60068-2-30, making it suitable for humidity cycling in mill or washdown-adjacent cabinets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E0901F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E0901F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}