{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E12008N5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E12008N5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E12008N5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E12008N5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, 4-pole, 32 A AC-1 at ≤415 V, 415 V AC 50 Hz coil, screw-clamp terminals, IP20, DIN-rail or plate mount.","salesMarkdown":"The coil is a wide-range AC type at 415 V 50 Hz, with a dropout threshold of 0.3 to 0.6 Uc and an operational range of 0.7 to 1.25 Uc across -5 to 55 °C — so it holds in nicely during brownout conditions but drops cleanly when the control signal goes low. It carries no built-in auxiliary contacts, so you'll need to add a separate auxiliary block if you want feedback or interlocking. The 45 mm width and 80 mm depth keep the footprint tight for a 4-pole unit. Connections are screw-clamp terminals — power circuit accepts 1 to 6 mm² solid or 1 to 4 mm² flexible with ferrules; control circuit takes 1 to 6 mm² solid or 1 to 4 mm² flexible. Torque both circuits to 1.2 N.m. IP20 protection means the contactor is safe from finger contact but not for washdown — keep it inside the enclosure. ## What the ratings mean in practice The AC-1 utilisation category tells you this contactor is optimised for resistive loads — think heaters, incandescent lighting, or transformer primary switching where the inrush is low. The rated breaking capacity of 96 A at 440 V and making capacity of 120 A at 440 V give you headroom for occasional overloads during fault clearing. Electrical durability is 300,000 cycles under AC-1, and mechanical durability is 10 million cycles — so in a heater-bank application cycling a few times an hour, the electrical life will be the limiting factor.","metaTitle":"Schneider Electric LC1E12008N5WBIN Easy TeSys Contactor, 32","metaDescription":"Active-production 4-pole contactor from Schneider Electric Easy TeSys range. Rated 32 A AC-1 at ≤415 V, 415 V AC 50 Hz coil. DIN-rail or plate mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 32 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"300000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"32 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 1 1...6 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"96 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"120 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"2.6 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"32 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.27 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"105 A 40 °C - 10 s for power circuit 61 A 40 °C - 60 s for power circuit 30 A 40 °C - 600 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/539cc07aea1922c8fe117fecf2d74c21.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E12008N5WBIN/contactoreasy-tesys-controllc1e4p2no+2ncac1415v32a415v50hz-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E12008N5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative if I need auxiliary contacts?","answer":"This contactor ships without auxiliary contacts. If your circuit requires feedback or interlocking, you will need to add a separate auxiliary contact block from the Easy TeSys range. There is no pin-compatible variant that includes built-in auxiliaries — the LC1E family is designed modularly."},{"question":"What compliance documentation does this part carry?","answer":"The contactor is certified to EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents. It carries an IP20 rating per IEC 60529 and a TH protective treatment per IEC 60068 for tropical environments. Fire resistance is tested at 850 °C per IEC 60695-2-1."},{"question":"What is the physical size for panel layout?","answer":"Width is 45 mm, depth is 80 mm, height is 74 mm. It mounts on DIN rail or directly to a plate. The screw-clamp terminals need access for a screwdriver, so allow clearance above and below for wiring."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E12008N5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E12008N5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}