{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E1201E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E1201E7","canonicalUrl":"https://aoctrl.com/schneider/LC1E1201E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E1201E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E1201E7, 3-pole contactor, 12 A AC-3 at ≤440 V, 48 V AC 50/60 Hz coil, 1 NC auxiliary contact.","salesMarkdown":"The LC1E1201E7 is a 3-pole contactor from Schneider Electric's Easy TeSys Control range, rated 12 A in AC-3 duty at ≤440 V — that's the motor-switching current, not the resistive load rating. It's certified to EN/IEC 60947-4-1 (the contactor standard) and EN/IEC 60947-5-1 (control-circuit devices), plus the GB/T equivalents for Chinese markets. Fire resistance tested to 850 °C per IEC 60695-2-1, so it's acceptable for appliance and HVAC panels that require glow-wire compliance. IP2X finger-safe terminals; wire it with the panel dead, as the front face doesn't fully shroud the busbars. Non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation. That matters if you're interlocking a reversing starter — the NC drops before the NO picks up, so you don't get a phase-to-phase short on the transition. ## Where it fits in a panel This is a motor-control contactor sized for a 12 A AC-3 load — think small conveyors, fans, pumps up to about 5.5 kW at 400 V. It also carries AC-3e for enhanced motor-switching endurance. Altitude rated to 3000 m without derating, so it works in high-altitude installations without recalculating the thermal curve. The TH protective treatment (pollution degree 3 per IEC 60068-2-30) means it's tested for humid, mildly corrosive environments — typical for a non-climate-controlled industrial panel, not for direct washdown.","metaTitle":"Schneider LC1E1201E7 Easy TeSys Contactor, 12A AC-3, 48V Coi","metaDescription":"Schneider Electric LC1E1201E7 Easy TeSys Control contactor. 3-pole, 12A AC-3 at ≤440V, 48V AC 50/60Hz coil. Active production. DIN rail mount. EN/IEC 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","title":"LC1E1201E7","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","description":"Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,12A,48V AC coil,50/60Hz,1NC auxiliary contact","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4655ed7f7f69be58ae517b69aaae12ac.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E1201E7/contactoreasy-tesys-controllc1e3p3noac3440v12a48v-ac-coil50-60hz1nc-auxiliary-contact/"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The headline rating is 12 A in AC-3 (motor-switching) duty at ≤440 V. The coil is 48 V AC, 50/60 Hz. It has 3 main poles (3NO) and 1 NC auxiliary contact. Dimensions are 45 mm wide, 74 mm high, 80 mm deep."},{"question":"What standards does this contactor comply with?","answer":"It meets EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, plus the Chinese GB/T 14048 series. Fire resistance is tested to 850 °C per IEC 60695-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E1201E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E1201E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}