{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E18004N5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E18004N5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E18004N5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E18004N5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E18004N5WBIN, 4-pole, 40 A AC-1 at 415 V, 415 V AC 50 Hz coil, screw-clamp terminals, DIN rail mount.","salesMarkdown":"The coil is 415 V AC 50 Hz wide-range, with a drop-out threshold of 0.3 to 0.6 Uc and pick-up at 0.7 to 1.25 Uc across the operating temperature range. The 4 NO pole configuration means no auxiliary contacts are built in — if you need feedback or a holding circuit, plan for an external auxiliary block. The headline number is 40 A at 415 V in AC-1 duty. That is the resistive-load rating; do not apply it to motor starting without consulting the AC-3 curve. The rated breaking capacity is 144 A at 440 V, and the making capacity is 180 A at 440 V — both under IEC 60947-4-1, so the contactor handles the brief surge of a cold resistive load without welding. Heat dissipation runs 2 to 3 W on the control circuit and 2.6 W per pole in AC-1, which matters for enclosure thermal management if you are packing several units side by side. The maximum operating rate is 1800 cycles per hour at 60 °C.","metaTitle":"Schneider Electric LC1E18004N5WBIN Easy TeSys Contactor, 40","metaDescription":"Schneider Electric LC1E18004N5WBIN Easy TeSys Control contactor. 40 A rated operational current at 415 V AC-1, 4 NO poles, 415 V AC 50 Hz coil. Current lifecycle stage. Sourced to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 40 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Power circuit: 1.2 N.m Control circuit: 1.2 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"300000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","Associated fuse rating":"40 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 1.5...6 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1.5...6 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"144 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"180 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"2.6 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"40 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.21 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"145 A 40 °C - 10 s for power circuit 84 A 40 °C - 60 s for power circuit 40 A 40 °C - 600 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E18004N5WBIN/easy-tesys-contactor-4p4no-60a-ac1-up-to-415v-coil-415v-ac-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E18004N5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative in the Easy TeSys family?","answer":"Within the same Easy TeSys Control range, a peer contactor with the same 4-pole, 40 A AC-1 rating but a different coil voltage (e.g., 230 V AC) would be the LC1E18004N7. The deciding factor for this variant is the 415 V AC 50 Hz coil — match the control voltage to your panel supply."},{"question":"What are the key ratings for this contactor?","answer":"Rated operational current is 40 A at ≤415 V AC in AC-1 (resistive load). Coil is 415 V AC 50 Hz. Breaking capacity is 144 A at 440 V; making capacity is 180 A at 440 V. Mechanical life is 10 million cycles; electrical life under AC-1 is 300,000 cycles."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E18004N5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E18004N5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}