{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E18008U7IN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E18008U7IN","canonicalUrl":"https://aoctrl.com/schneider/LC1E18008U7IN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E18008U7IN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E18008U7IN, 4-pole contactor (2NO+2NC), AC-1 rated 40A at ≤415V, IP2X, DIN rail mount.","salesMarkdown":"## What this contactor is — and what it's not Its AC-1 utilisation category means it's designed for resistive loads. The rated operational voltage on the power circuit is ≤415 V, and it carries a 40 A rating in that duty. If you're sourcing this for a motor load, stop: AC-3 (inductive motor duty) is a different rating curve, and this part doesn't carry one on record. ## Mounting and integration notes Mounts on a plate or DIN rail. The footprint is 45 mm wide by 74 mm tall by 80 mm deep. IP2X protection means it's finger-safe from the front but not sealed against dust or moisture; keep it inside an enclosure. The AC-1 rating of 40 A at ≤415 V tells you the continuous current-carrying capacity for resistive loads. That's the number that governs the contactor's thermal sizing — don't derate it for motor inrush unless you know the AC-3 value (which isn't listed here). The non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation is a safety feature: it guarantees that the NC and NO poles never close simultaneously during transition, which matters if you're using the NC for a safety feedback loop and the NO for the load circuit. ## Standards and environmental limits Operating altitude up to 3000 m without derating, and the permissible ambient temperature range is -5 °C to +55 °C for operation, with storage from -60 °C to +80 °C.","metaTitle":"Schneider Electric LC1E18008U7IN Easy TeSys Contactor, 4P, 4","metaDescription":"Obsolete Schneider LC1E18008U7IN Easy TeSys contactor, 4P (2NO+2NC), 40A AC-1 at ≤415V. Sourced to order against RFQ. Standards EN/IEC 60947. DIN rail mount.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"4P","Operating altitude":"3000 m","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e1f4153dabd2a6b9c547b9e07aba5e78.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E18008U7IN/contactoreasy-tesys-controllc1e4p2no+2ncac1415v40a240v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E18008U7IN/alternatives.json"},"ai":{"faq":[{"question":"What standards does this contactor comply with?","answer":"It meets EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T 14048.1, 14048.4, and 14048.5 equivalents. Fire resistance is tested to 850 °C per IEC 60695-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E18008U7IN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E18008U7IN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}