{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E1801P7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E1801P7","canonicalUrl":"https://aoctrl.com/schneider/LC1E1801P7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E1801P7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E1801P7, 3P (3NO), AC-3/AC-3e ≤440V, 18A, 230V AC coil, 1NC auxiliary contact.","salesMarkdown":"The Schneider Electric LC1E1801P7 is a 3-pole contactor from the Easy TeSys Control range, rated for 18 A in AC-3 duty at up to 440 V with a 230 V AC coil and one normally-closed auxiliary contact. It is designed for motor control and resistive load switching, covering the AC-3, AC-3e, and AC-1 utilisation categories. The AC-3 rating (18 A) is the key figure for motor starting — it governs the contactor's ability to handle the inrush current of a squirrel-cage motor during start-up and break the running current. The AC-1 rating covers resistive loads like heaters, where the switching duty is less severe. Dimensions are 80 mm deep by 74 mm high — factor that into your enclosure fill and gland-plate clearance. The IP2X degree of protection means it is finger-safe but not sealed against dust or moisture — install inside a panel with an appropriate enclosure rating for the environment. Operates from -5 °C to 55 °C ambient, with storage from -60 °C to 80 °C. The TH protective treatment (pollution degree 3) per IEC 60068-2-30 means it withstands humid, tropical conditions — relevant for unheated enclosures or coastal sites. Fire resistance tested to 850 °C per IEC 60695-2-1. Also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance applications. ## Mechanical and timing notes The non-overlap time between NC and NO contacts is guaranteed at 1.5 ms on both energisation and de-energisation — important for interlocking circuits where you need to ensure one set of contacts opens before the other closes. Mechanical robustness: withstands 1.5 Gn vibration (open) and 3 Gn (closed) across 5–300 Hz, plus shock ratings of 7 Gn (open) and 10 Gn (closed) for 11 ms. Suitable for applications with moderate vibration, such as conveyor systems or pump panels.","metaTitle":"Schneider Electric LC1E1801P7 Easy TeSys Contactor, 18A, 230","metaDescription":"Schneider Electric LC1E1801P7 Easy TeSys Control contactor, 3P, 18A AC-3, 230V AC coil, 1NC aux. Active production. DIN rail mount. EN/IEC 60947 compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","title":"LC1E1801P7","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","description":"Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3/AC-3e,<=440V,18A,230V AC coil,1NC auxiliary contact","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5b234cf8ac8f216c7013a0e21733acff.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1E1801P7/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v18a230v-ac-coil1nc-auxiliary-contact/"},"ai":{"faq":[{"question":"What are the key ratings for the LC1E1801P7?","answer":"The LC1E1801P7 is a 3-pole contactor rated 18 A in AC-3 duty at ≤440 V with a 230 V AC coil. It includes one normally-closed auxiliary contact and covers AC-3, AC-3e, and AC-1 utilisation categories."},{"question":"What compliance standards does the LC1E1801P7 meet?","answer":"It complies with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1, 14048.4, 14048.5, and relevant clauses of EN/IEC 60335-1 and -2-40. Fire resistance is tested to 850 °C per IEC 60695-2-1."},{"question":"What is the mounting method for the LC1E1801P7?","answer":"It mounts on a DIN rail or plate. Dimensions are 45 mm wide, 80 mm deep, and 74 mm high."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E1801P7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E1801P7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}