{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E1810BD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E1810BD","canonicalUrl":"https://aoctrl.com/schneider/LC1E1810BD","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E1810BD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E1810BD, 3-pole contactor, 18 A AC-3/AC-3e at ≤440 V, 24 V DC coil, 1 N/O auxiliary contact, DIN rail mount.","salesMarkdown":"The LC1E1810BD is a 3-pole contactor from the Easy TeSys Control range, rated 18 A in AC-3 duty at ≤440 V. The 24 V DC coil is the control voltage; the 1 N/O auxiliary contact provides a feedback signal. AC-1 resistive load capability is also listed, so the same contactor handles non-inductive heating or lighting loads at its full thermal current rating. The AC-3e category aligns with energy-efficient motor applications where the contactor must handle higher inrush from premium-efficiency motors. IP20 finger-safe enclosure per IEC 60529. Mounts on DIN rail or plate, 45 mm wide. The 18 A AC-3 rating covers small conveyors, pumps, fans, and compressors up to roughly 7.5 kW at 400 V three-phase. The 24 V DC coil is common in PLC-controlled or safety-relay-driven circuits where low-voltage control is preferred. Storage range extends to -60 °C to +80 °C, which matters for unheated warehouses. Compliance with EN/IEC 60947-1, 60947-4-1, and 60947-5-1 covers the product standard for contactors and motor-starters, plus the control-circuit device standard. The GB/T equivalents (GB/T 14048.1, 14048.4, 14048.5) satisfy CCC requirements for the Chinese market.","metaTitle":"LC1E1810BD Easy TeSys Contactor, 18A AC-3, 24V DC Coil","metaDescription":"LC1E1810BD Easy TeSys Control 3-pole contactor, 18A AC-3/AC-3e at 440V, 24V DC coil, 1 N/O aux. Active production. DIN rail mount. IP20. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"45 mm","Height":"77 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor open (5 Gn for 11 ms) conforming to IEC 60068-2-7 Shocks contactor closed (10 Gn for 11 ms) conforming to IEC 60068-2-7 Vibrations contactor open (1.5 Gn, 5...300 Hz) conforming to IEC 60068-2-6 Vibrations contactor closed (3 Gn, 5...300 Hz) conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for signalling circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2d13216f36fd59ca4450eeeffdbe9dfa.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1E1810BD/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v18a24v-dc-coil1-no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E1810BD/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E1810BD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E1810BD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}