{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E1810F6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E1810F6","canonicalUrl":"https://aoctrl.com/schneider/LC1E1810F6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E1810F6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E1810F6, 3P contactor, AC-3/AC-3e 18 A, 110 V AC coil 60 Hz, 1 NO auxiliary contact.","salesMarkdown":"It carries an AC-3 utilisation category rating of 18 A at up to 440 V, meaning it's sized for switching three-phase induction motors on and off under load — the standard duty cycle for conveyor drives, pumps, and compressors. The 110 V AC coil at 60 Hz matches North American control voltage common in older panels and retrofit work. The AC-1 rating covers resistive loads like heaters, where the switching current is lower due to no inrush. The 110 V AC coil draws its control power from a separate circuit — verify the control transformer is sized for the coil inrush if you're replacing a different coil voltage variant. The contactor carries a 1.5 ms non-overlap time between NC and NO contacts, which matters if you're using the auxiliary for interlocking — it guarantees the NC opens before the NO closes on energisation, and vice versa on de-energisation. TH protective treatment per IEC 60068-2-30 means it's tested for damp heat, so condensation in an unheated enclosure won't cause early failure. Certified to EN/IEC 60947-1 (general rules), 60947-4-1 (contactors and motor-starters), and 60947-5-1 (control-circuit devices). Also meets GB/T equivalents for the Chinese market and EN/IEC 60335-1 Clause 30.2 for glow-wire resistance in household appliances.","metaTitle":"Schneider Electric LC1E1810F6 Easy TeSys Contactor, 18A AC-3","metaDescription":"Obsolete Schneider LC1E1810F6 Easy TeSys contactor, 3P, 18A AC-3, 110V AC 60Hz coil, 1NO aux. Sourced to order against RFQ. EN/IEC 60947 certified.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"80 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/516eac39a3a39e831def6cb851a519e4.pdf","sourceUrl":"https://www.se.com/sa/en/product/LC1E1810F6/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v18a110v-ac-coil60hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E1810F6/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LC1E1810F6?","answer":"It is a 3-pole contactor rated 18 A in AC-3 (motor switching) at up to 440 V, with a 110 V AC 60 Hz coil and one normally open auxiliary contact. It also carries AC-1 and AC-3e utilisation categories."},{"question":"What standards does the LC1E1810F6 comply with?","answer":"It complies with EN/IEC 60947-1, 60947-4-1, 60947-5-1, GB/T 14048.1, 14048.4, 14048.5, and EN/IEC 60335-1 Clause 30.2. Fire resistance tested at 850 °C per IEC 60695-2-1."},{"question":"How is the LC1E1810F6 mounted?","answer":"It mounts on a DIN rail or plate. Dimensions are 45 mm wide, 74 mm high, 80 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E1810F6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E1810F6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}