{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E200ASCH2S260N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E200ASCH2S260N","canonicalUrl":"https://aoctrl.com/schneider/LC1E200ASCH2S260N","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E200ASCH2S260N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E200ASCH2S260N, 1-pole DC contactor, 200 A continuous (Ith), 12 V DC coil, IEC 60947-4-1.","salesMarkdown":"## DC Contactor for High-Voltage Switching It switches DC circuits up to 1000 V, making it suited for high-voltage battery banks, power supplies, or inverter DC links. The coil is 12 V DC, with a pull-in power of 32 W and a hold-in of 3.5 W. Minimum switching capability goes down to 0.1 A at 8 V DC, so it can handle low-level signals as well as high-current paths. Mechanical endurance is 300,000 cycles; electrical durability at full rating is 1500 make/break cycles at 750 V DC and 1000 cycles at 1000 V DC. ## Ratings That Matter for Integration The contactor carries short-time ratings that let it handle overloads: 250 A for 15 minutes, 320 A for 5 minutes, 600 A for 30 seconds, and 900 A for 10 seconds. That gives headroom for inrush without immediate derating. Insulation voltage is 1500 V, impulse withstand 8 kV (coil not connected to power circuit). Altitude capability is 4000 m without derating. Vibration resistance is 5 g from 10 to 500 Hz; shock is 20 g for 11 ms. These ratings support use in mobile or industrial environments. ## Mounting & Wiring Notes Mounts vertically; dimensions are 3.2 in deep, 2.6 in wide, 2.9 in tall. Power terminals accept M8 bolts with flat and spring washers, torque to 70.8–88.5 lbf·in (8–10 N·m). The control circuit is a 2-wire DC supply with 15.7 in (40 cm) leads. IP60 protection means dust-tight but not waterproof. One NO auxiliary contact is built in.","metaTitle":"Schneider LC1E200ASCH2S260N Easy TeSys DC Contactor 200A 12V DC | aoctrl","metaDescription":"Schneider LC1E200ASCH2S260N Easy TeSys contactor for charging: 200A, 12V DC coil, double pole, DC-1 <=1000V. Authorized distributor. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"3.2 in (81.3 mm)","Range":"Easy TeSys","Width":"2.6 in (66.5 mm)","title":"LC1E200ASCH2S260N","Height":"2.9 in (74.3 mm)","Category":"US10I1222354","Polarity":"No main contact Yes coil","Standards":"IEC 60947-4-1 GB/T 14048.4","description":"Contactor for charging post,Easy TeSys Control,DC-1 <=1000V 200A,12V DC, double coils,epoxy,external thread,without connector","Operating time":"30 ms on closing 15 ms on opening","lifecycle_stage":"current","Mounting Support":"Vertical support","Range of Product":"Easy TeSys Control","Average impedance":"0.5 mOhm - Ith 200 A","Device short name":"LC1E","Inrush power in W":"32 W","Poles description":"1P","Tightening torque":"Power circuit 70.8...88.5 lbf.in (8...10 N.m)","Operating altitude":"13123.36 ft (4000 m) without derating","End Connection Type":"External thread","Control circuit type":"DC","Contactor application":"Resistive load","Electrical durability":"1500 cycles at 750 V, 200 A on resistive load for only breaking, 0.6s open, 5.4s break 1000 cycles at 1000 V, 200 A on resistive load for only breaking, 0.6s open, 5.4s break","Insulation resistance":"1000 MOhm at 1000 V DC","Mechanical durability":"300000 cycles","Mechanical robustness":"Vibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit M8 Bolt Power circuit flat washers Power circuit spring washers Control circuit 2-wire supply 15.7 in (40 cm)","IP degree of protection":"IP60","Pole contact composition":"1 NO","Maximum switching voltage":"1000 V DC","Minimum switching current":"0.1 A","Minimum switching voltage":"8 V for DC","Product or Component Type":"Contactor","[Uc] control circuit voltage":"12 V DC","Auxiliary contact composition":"1 NO","Permissible short-time rating":"200 A for continuous 250 A 15 min 320 A 5 min 600 A 30 s 900 A 10 s","[Ui] rated insulation voltage":"1500 V IEC 60947-4-1 power circuit","Control circuit voltage limits":"0.85...1.1 Uc operational 0.1...0.75 Uc drop-out","Hold-in power consumption in W":"3.5 W","Ambient air temperature for operation":"-40...185 °F (-40...85 °C) operation -40...185 °F (-40...85 °C) storage","[Uimp] rated impulse withstand voltage":"8 kV coil not connected to the power circuit IEC 60947","[Ith] conventional free air thermal current":"200 A for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$400.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a2bcaa14994ce73faad3b053c2567b9b.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1E200ASCH2S260N/contactor-for-charging-posteasy-tesys-controldc1-1000v-200a12v-dc-double-coilsepoxyexternal-threadwithout-connector/"},"ai":{"faq":[{"question":"What is the maximum DC switching voltage?","answer":"The contactor can switch up to 1000 V DC, with a rated impulse withstand of 8 kV."},{"question":"What coil voltage does this contactor use?","answer":"The control circuit voltage is 12 V DC, with an operating range of 0.85 to 1.1 Uc for pick-up and drop-out between 0.1 and 0.75 Uc."},{"question":"What is the depth of this contactor?","answer":"Listed depth is 3.2 inches (81.3 mm)."},{"question":"What product range is this from?","answer":"It belongs to the Schneider Electric Easy TeSys Control range of contactors."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E200ASCH2S260N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E200ASCH2S260N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}