{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E25004Q7IN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E25004Q7IN","canonicalUrl":"https://aoctrl.com/schneider/LC1E25004Q7IN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E25004Q7IN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E25004Q7IN, 4P(4NO) contactor, AC-1 50A ≤415V, 380V coil.","salesMarkdown":"It is rated for AC-1 utilisation category at 50 A up to 415 V, meaning it is designed for resistive load switching — heating elements, lighting banks, or other loads where the inrush current is low relative to the steady-state current. The coil is wound for 380 V control voltage. The IP2X degree of protection (finger-safe) is adequate for enclosed panel installation where the front face is behind a panel door. It also meets the Chinese GB/T equivalents of these standards. Mechanical robustness is specified for vibration (1.5 Gn open, 3 Gn closed) and shock (6 Gn open, 10 Gn closed). Maximum operating altitude is 3000 m.","metaTitle":"Schneider Easy TeSys LC1E25004Q7IN Contactor, 4P, AC-1 50A","metaDescription":"Schneider Electric Easy TeSys Control LC1E25004Q7IN contactor, 4P (4NO), AC-1 rated 50A at ≤415V. Obsolete — sourced to order against RFQ. EN/IEC 60947 compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"56 mm","Height":"64 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"4P","Operating altitude":"3000 m","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/464cf8b45dd65bee795173f148bd6de0.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E25004Q7IN/contactoreasy-tesys-controllc1e4p4noac1415v50a380v/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E25004Q7IN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a 4-pole (4NO) contactor rated for AC-1 utilisation category at 50 A, with a maximum operational voltage of 415 V. The coil is 380 V. It is designed for resistive load applications."},{"question":"What standards does this contactor comply with?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the corresponding Chinese GB/T standards. Fire resistance is tested to 850 °C per IEC 60695-2-1."},{"question":"What is the mounting method and physical size?","answer":"It mounts on a DIN rail or plate. Dimensions are 56 mm wide, 64 mm high, and 93 mm deep."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E25004Q7IN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E25004Q7IN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}