{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E25008M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E25008M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E25008M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E25008M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, contactor LC1E25008M5WBIN, 4 poles, 50 A AC-1, 220 V AC 50 Hz coil, screw clamp terminals, DIN rail mounting.","salesMarkdown":"The Schneider Electric LC1E25008M5WBIN is a 4-pole contactor from the Easy TeSys Control range, rated for 50 A at ≤415 V AC in AC-1 utilisation category — meaning it's sized for resistive loads like heaters or lighting banks, not motor starting. The 220 V AC 50 Hz coil is wide-range, holding in at 0.7–1.25 Uc and dropping out at 0.3–0.6 Uc across -5 to 55 °C. Pole configuration is 2 NO + 2 NO (four poles total), with no auxiliary contact block fitted — you'll add one if you need feedback to a PLC or status indication on the panel door. The headline 50 A AC-1 rating is the continuous resistive current at ≤40 °C — that's the number that governs your bus bar and cable sizing for a heater or transformer load. Don't confuse it with an AC-3 motor rating; this contactor is listed for resistive duty only per the utilisation category. Breaking capacity is 200 A at 440 V, making capacity 250 A at 440 V, so it handles inrush from cold resistive elements without welding. Mechanical durability of 10 million cycles and electrical durability of 350,000 cycles at AC-1 tell you it's built for frequent switching in a process line, not a once-a-day HVAC contactor. ## Mounting, wiring, and panel integration Power circuit terminals accept up to 10 mm² flexible with cable end, control circuit up to 4 mm². Tightening torque is 1.5 N·m on power, 1.2 N·m on control — use a torque screwdriver; overtightening strips the screw clamp on these smaller terminals.","metaTitle":"Schneider Electric LC1E25008M5WBIN Easy TeSys Contactor, 50","metaDescription":"Schneider Electric LC1E25008M5WBIN Easy TeSys 4-pole contactor, 50 A AC-1 rated operational current, 220 V AC 50 Hz coil. Active lifecycle, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 50 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 1.5 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"10000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","Associated fuse rating":"50 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...6 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 1.5...10 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1.5...10 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"200 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"250 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"3.2 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"50 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"240 A 40 °C - 10 s for power circuit 120 A 40 °C - 60 s for power circuit 50 A 40 °C - 600 s for power circuit","[Ith] conventional free air thermal current":"50 A (at 40 °C) for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E25008M5WBIN/easy-tesys-contactor-4p-ctr-100a-ac12no+2nc220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E25008M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The two critical specs are the 50 A rated operational current in AC-1 (resistive load) at ≤415 V AC, and the 220 V AC 50 Hz control coil voltage. Pole configuration is 4 poles (2 NO + 2 NC)."},{"question":"What compliance standards does this contactor meet?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the Chinese GB/T equivalents GB/T 14048.1, GB/T 14048.4, GB/T 14048.5. Fire resistance is 850 °C per IEC 60695-2-1."},{"question":"Does it include auxiliary contacts?","answer":"No, the contactor ships without auxiliary contacts — the pole contact composition is 2 NO + 2 NC on the main poles only. You will need to add a separate auxiliary contact block if you require feedback or status signaling."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E25008M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E25008M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}