{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E2510BD","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E2510BD","canonicalUrl":"https://aoctrl.com/schneider/LC1E2510BD","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E2510BD","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, contactor LC1E2510BD, 3P(3NO), AC-3/AC-3e ≤440 V 25 A, 24 V DC coil, 1 N/O auxiliary contact.","salesMarkdown":"The LC1E2510BD is a 3-pole contactor rated 25 A in AC-3 duty (motor switching) at ≤440 V, so it directly controls a 3-phase induction motor up to roughly 7.5 kW at 400 V. The same pole set also carries an AC-1 resistive load rating — useful for heater banks or lighting where inrush is minimal. The AC-3e category means it's tested for the enhanced electrical endurance profile typical of modern motor starters. The 24 V DC coil keeps it compatible with PLC-driven or safety-relay outputs without an intermediate interface relay. The 45 mm width fits a standard 4-module slot in a DIN-rail enclosure. IP20 finger-safe terminals mean it can sit in an open panel without additional shrouding — standard for control cabinets. The 93 mm depth leaves clearance for wiring ducts or a second row of components. Certified to EN/IEC 60947-4-1 (contactors and motor-starters) and EN/IEC 60947-5-1 (control-circuit devices). Also carries GB/T equivalents for the Chinese market. Fire resistance rated 850 °C per IEC 60695-2-1. Protective treatment TH (IEC 60068-2-30) means it withstands tropical humid conditions — no additional conformal coating needed for most indoor environments.","metaTitle":"Schneider Electric LC1E2510BD Easy TeSys Contactor, 25A AC-3","metaDescription":"Active 3-pole contactor for motor control. 25 A AC-3/AC-3e at ≤440 V. 24 V DC coil, 1 N/O auxiliary. IP20, DIN-rail or plate mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"45 mm","Height":"77 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Shocks contactor open (5 Gn for 11 ms) conforming to IEC 60068-2-7 Shocks contactor closed (10 Gn for 11 ms) conforming to IEC 60068-2-7 Vibrations contactor open (1.5 Gn, 5...300 Hz) conforming to IEC 60068-2-6 Vibrations contactor closed (3 Gn, 5...300 Hz) conforming to IEC 60068-2-6","IP degree of protection":"IP20 conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for signalling circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/07187fbc4997939b8b6e82e2defb772c.pdf","sourceUrl":"https://www.se.com/mk/en/product/LC1E2510BD/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v25a24v-dc-coil1-no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E2510BD/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative in the same family?","answer":"Within the Easy TeSys Control range, the LC1E2510M7 uses a 220 V AC 50 Hz coil instead of 24 V DC. The mechanical and pole ratings are identical — the coil voltage is the only difference. If your control voltage is fixed at 24 V DC, stick with the BD variant."},{"question":"What compliance documentation is available?","answer":"The contactor is certified to EN/IEC 60947-1, 60947-4-1, and 60947-5-1, plus the Chinese GB/T equivalents. Fire resistance is tested to IEC 60695-2-1 at 850 °C. Protective treatment TH per IEC 60068-2-30 covers humid environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E2510BD","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E2510BD when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}