{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E2510E7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E2510E7","canonicalUrl":"https://aoctrl.com/schneider/LC1E2510E7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E2510E7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E2510E7, 3P contactor, 25 A AC-3 at ≤440 V, 48 V AC 50/60 Hz coil, 1 NO auxiliary contact, DIN rail mount.","salesMarkdown":"The LC1E2510E7 is a 3-pole contactor from Schneider's Easy TeSys Control range, rated 25 A in AC-3 duty at ≤440 V — that's the motor-switching current for a typical 7.5 kW induction motor on a 400 V line. The AC-3e category adds an energy-efficiency curve for modern high-efficiency motors, while AC-1 (resistive) rating covers heater banks or lighting loads. The 1.5 ms guaranteed non-overlap time between NC and NO contacts on both energisation and de-energisation means this contactor can be used in reversing or star-delta starters where a momentary short-circuit across phases would be catastrophic. That timing is built into the contactor's mechanical interlock, not dependent on external logic. ## Panel integration and environmental limits Mounts on either a DIN rail or plate, with a 45 mm width footprint — three of these fit in a standard 145 mm wide enclosure section. IP2X finger protection means it's safe for open-panel mounting where operators reach in, but not for washdown environments. The TH protective treatment (pollution degree 3 per IEC 60068-2-30) handles humid, mildly corrosive atmospheres typical of HVAC plant rooms or agricultural buildings. No derating needed up to 3000 m altitude — useful for high-altitude installations where many contactors lose capacity above 2000 m.","metaTitle":"Schneider LC1E2510E7 Easy TeSys Contactor, 25A AC-3, 48V AC","metaDescription":"Schneider Electric LC1E2510E7 Easy TeSys Control contactor. 3P (3NO), AC-3 rated 25A at ≤440V, 48V AC 50/60Hz coil, 1NO aux. Active production. DIN rail mount. EN/IEC 60947 complia","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"85 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f4280b509e40bf38587b29728dc42403.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E2510E7/contactoreasy-tesys-controllc1e3p3noac3440v25a48v-ac-coil50-60hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E2510E7/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative to LC1E2510E7 in the Easy TeSys family?","answer":"Within the same Easy TeSys Control range, the LC1E2510M7 uses a 48 V DC coil instead of the 48 V AC coil on this part. The mechanical footprint, pole configuration, and AC-3 current rating are identical, so the choice comes down to control voltage — swap only if your control circuit is DC rather than AC."},{"question":"What compliance documentation is available for this contactor?","answer":"The LC1E2510E7 is certified to EN/IEC 60947-1, -4-1, and -5-1, plus the Chinese GB/T equivalents. It also meets the glow-wire test at 850 °C per IEC 60695-2-1 and the household appliance standard EN/IEC 60335-1 Clause 30.2. CE marking applies for European markets; UL/CSA listing is covered under the TeSys family certification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E2510E7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E2510E7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}