{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E2510N5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E2510N5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E2510N5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E2510N5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E2510N5WB, 3-pole contactor, AC-3 400 V 25 A, 415 V AC wide-range coil, DIN-rail or plate mount, IP20.","salesMarkdown":"The Schneider Electric LC1E2510N5WB is a 3-pole contactor from the Easy TeSys Control range, rated 25 A in AC-3 utilisation category at 400 V — that's the motor-switching current, so it handles a 3-phase induction motor up to roughly 11 kW at 400 V without derating. The coil is 415 V AC wide-range, meaning it pulls in reliably across a band of supply voltages, not just a single nominal. It also carries an AC-1 resistive load rating for heater or lighting circuits. The AC-3e suffix means it's also tested for energy-efficient motors with higher inrush, common in modern IE3/IE4 classes. For resistive loads (AC-1), the thermal current is higher — the datasheet curve governs the exact figure, but the contactor body is sized for the 25 A AC-3 frame. The 415 V AC coil is a wide-range type, so it operates across a voltage band (typically 0.85 to 1.1 x Uc, though the exact hold/dropout thresholds are in the datasheet). This matters if your control transformer is tapped at 400 V or 480 V — the wide-range coil avoids a separate coil changeout. The permissible ambient is -20 to 70 °C at coil rated voltage, with operation limited to -5 to 55 °C. Below that, no reduction in ratings. Mounts on DIN rail (35 mm symmetrical rail) or directly to a plate via screws. IP20 means finger-safe terminals but no washdown protection — keep it inside a sealed cabinet or a clean indoor panel. The 3-pole configuration (3 NO main poles) suits a standard three-phase motor circuit. No built-in auxiliary contacts on this variant — add a side-mount auxiliary block if you need feedback to a PLC or status indication. Also complies with EN/IEC 60335-1 Clause 30.2 for glow-wire and EN/IEC 60335-2-40 Annex JJ for heat-pump applications. Protective treatment TH per IEC 60068-2-30 means it withstands tropical humid conditions — relevant for export or coastal installations.","metaTitle":"Schneider Easy TeSys LC1E2510N5WB Contactor, 25 A AC-3, 415","metaDescription":"Active LC1E2510N5WB contactor, 3P, 25 A at 400 V AC-3, 415 V AC coil wide range. DIN-rail mount, IP20, IEC 60947. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"85 mm","Range":"Easy TeSys","Width":"45 mm","Height":"74 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP20 conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for signalling circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E2510N5WB/easy-tesys-contactor-3p3-no-ac3-400-v-25a-415-v-ac-coil-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E2510N5WB/alternatives.json"},"ai":{"faq":[{"question":"What is the closest alternative within the Easy TeSys family?","answer":"The LC1E2510N5WB is a specific variant with a 415 V AC wide-range coil. The closest sibling would be the same 25 A AC-3 frame with a different coil voltage (e.g., 24 V AC, 230 V AC, or 24 V DC). The mechanical and pole configuration are identical; only the coil voltage changes. If your control voltage is fixed at 230 V or 24 V, order the corresponding coil code instead."},{"question":"What compliance documentation does Schneider provide for this part?","answer":"The contactor is certified to EN/IEC 60947-1, -4-1, and -5-1, plus GB/T 14048.1/4/5. It also meets EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ. Fire resistance is 850 °C per IEC 60695-2-1. Protective treatment TH per IEC 60068-2-30. RoHS and REACH declarations are standard from Schneider."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E2510N5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E2510N5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}