{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E3201B6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E3201B6","canonicalUrl":"https://aoctrl.com/schneider/LC1E3201B6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E3201B6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E3201B6, 3P(3NO) contactor, AC-3/AC-3e ≤440V 32A, 24V AC 60Hz coil, 1NC auxiliary contact.","salesMarkdown":"The Schneider Electric LC1E3201B6 is a 3-pole contactor from the Easy TeSys Control range, rated for AC-3 and AC-3e duty at 32 A up to 440 V. It carries a 24 V AC 60 Hz coil and one normally-closed auxiliary contact. The 32 A AC-3 rating means it handles motor starting and running currents for loads up to that level — the rating that governs real-world motor switching, not the higher AC-1 resistive value. It also complies with EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for fire resistance — the housing withstands 850 °C glow-wire test per IEC 60695-2-1. The protective treatment 'TH' (pollution degree 3) per IEC 60068-2-30 means it tolerates humid, tropical environments — relevant for panels in non-conditioned factory spaces. Mechanical robustness: the contactor withstands 1.5 Gn vibration (5-300 Hz) when open, 3 Gn when closed, and 10 Gn shocks for 11 ms.","metaTitle":"LC1E3201B6 Easy TeSys Contactor, 32A AC-3, 24V AC, 3P, 1NC","metaDescription":"Obsolete LC1E3201B6 Easy TeSys Control contactor, 3P(3NO), AC-3/AC-3e ≤440V 32A, 24V AC 60Hz coil, 1NC aux. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1474e119cf74804b2e082537f6c606a3.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1E3201B6/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v32a24v-ac-coil60hz1nc-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E3201B6/alternatives.json"},"ai":{"faq":[{"question":"What replaces the LC1E3201B6?","answer":"There is no official manufacturer successor listed for this order code. A replacement would need to be selected based on matching the 24 V AC 60 Hz coil, 3-pole configuration, 32 A AC-3 rating, and 1NC auxiliary contact."},{"question":"What are the key ratings for the LC1E3201B6?","answer":"It is a 3-pole contactor rated 32 A in AC-3/AC-3e duty at ≤440 V, with a 24 V AC 60 Hz coil and one NC auxiliary contact. Dimensions: 84 mm high, 56 mm wide, 86 mm deep."},{"question":"What standards does the LC1E3201B6 comply with?","answer":"It meets EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1/4/5, and EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ. Fire resistance is 850 °C per IEC 60695-2-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E3201B6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E3201B6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}