{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E3210F7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E3210F7","canonicalUrl":"https://aoctrl.com/schneider/LC1E3210F7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E3210F7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E3210F7, 3P(3NO), AC-3/AC-3e ≤440V 32A, 110V AC 50/60Hz coil, 1NO auxiliary contact.","salesMarkdown":"The Schneider Electric LC1E3210F7 is a 3-pole contactor from the Easy TeSys Control range, rated for 32 A in AC-3/AC-3e duty at up to 440 V, with a 110 V AC 50/60 Hz coil and one normally-open auxiliary contact. The AC-3 rating (32 A ≤440 V) means it handles the inrush of a squirrel-cage motor during starting and breaks the running current — the critical figure for sizing a contactor to a motor load. The AC-3e variant adds an energy-efficiency classification per IEC 60947-4-1. Mounts on DIN rail or plate. IP2X finger protection is provided on the contactor body. Compliant with EN/IEC 60947-1, -4-1, -5-1 and GB/T 14048.1.4.5. Permissible ambient temperature: -20 to 70 °C at coil rated voltage, -60 to 80 °C storage, -5 to 55 °C operation. Mechanical robustness: vibrations 1.5 Gn open, 3 Gn closed; shocks 6 Gn open, 10 Gn closed.","metaTitle":"Schneider LC1E3210F7 Easy TeSys Contactor, 32A AC-3, 110V Co","metaDescription":"Schneider Electric LC1E3210F7 Easy TeSys Control contactor, 3P, 32A AC-3/AC-3e ≤440V, 110V AC 50/60Hz coil, 1NO aux. Obsolete — sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13cf81cb707ad4f9258c690bcf5eb0b1.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1E3210F7/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v32a110v-ac-coil50-60hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E3210F7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of the LC1E3210F7?","answer":"It is a 3-pole contactor rated 32 A in AC-3/AC-3e duty at ≤440 V, with a 110 V AC 50/60 Hz coil and one normally-open auxiliary contact. It also carries AC-1 resistive load ratings."},{"question":"What standards does the LC1E3210F7 comply with?","answer":"It complies with EN/IEC 60947-1, -4-1, -5-1, GB/T 14048.1.4.5, and EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for fire resistance. Fire resistance is verified at 850 °C per IEC 60695-2-1."},{"question":"How do I source the LC1E3210F7?","answer":"Because it is obsolete, no shelf stock is held. Submit an RFQ for a surplus or broker-channel quote. The part is quoted to order only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E3210F7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E3210F7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}