{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E3210N5WB","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E3210N5WB","canonicalUrl":"https://aoctrl.com/schneider/LC1E3210N5WB","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E3210N5WB","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys contactor, 3P (3 NO), AC-3 32 A at 400 V, 415 V AC wide-range coil, DIN-rail mount, IP20.","salesMarkdown":"The LC1E3210N5WB is a 3-pole (3 NO) contactor from Schneider Electric's Easy TeSys Control range, rated for AC-3 duty at 32 A at 400 V. It handles motor switching and resistive loads, with a 415 V AC wide-range coil that simplifies coil voltage selection across different line supplies. AC-3 rating at 32 A at 400 V. AC-1 resistive rating covers heater or lighting loads. Wide-range coil (415 V AC) simplifies panel wiring. IP20 finger-safe protection covers terminals. Ambient range -20 to 70 °C at the coil, with operation from -5 to 55 °C, covers most indoor industrial conditions. TH protective treatment per IEC 60068 handles tropical humidity — no extra conformal coating needed for damp environments. Mechanical robustness: the contactor withstands 3 Gn vibration when closed and 10 Gn shock when closed — enough for conveyor drives, compressors, and pump panels subject to normal industrial vibration. Compliant with EN/IEC 60947-1, -4-1, -5-1, and GB/T equivalents. Also listed under EN/IEC 60335-1. Lifecycle status is active. Sourced to order via RFQ.","metaTitle":"Schneider Electric LC1E3210N5WB Easy TeSys Contactor, 3P AC-","metaDescription":"Active Easy TeSys contactor, 3P NO, AC-3 32A at 400V, 415V AC wide-range coil. DIN-rail mount, IP20. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP20 conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for signalling circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E3210N5WB/easy-tesys-contactor-3p3-no-ac3-400-v-32a-415-v-ac-coil-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E3210N5WB/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"AC-3 rating: 32 A at 400 V. Coil: 415 V AC wide-range. Poles: 3 NO. Mounting: DIN rail or plate. IP20. Operating altitude: 3000 m without derating."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E3210N5WB","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E3210N5WB when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}