{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E3210R6","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E3210R6","canonicalUrl":"https://aoctrl.com/schneider/LC1E3210R6","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E3210R6","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E3210R6, 3P contactor, AC-3/AC-3e 32A ≤440V, 440V AC 60Hz coil, 1NO auxiliary contact.","salesMarkdown":"The Schneider Electric LC1E3210R6 is a three-pole contactor from the Easy TeSys Control range, rated for motor control in AC-3 and AC-3e duty up to 32 A at 440 V, with a 440 V AC 60 Hz coil and one normally open auxiliary contact. The AC-3 rating of 32 A at 440 V governs its motor-switching capability — this is the current it can make and break under full-load motor starting conditions, not just carry continuously. For resistive loads (AC-1), the contactor can handle higher currents, but the AC-3 figure is the one that decides fit for standard induction motor duty. The 440 V AC coil means it pulls in reliably on a 440 V control circuit at 60 Hz; verify your control transformer matches both voltage and frequency. The TH protective treatment per IEC 60068-2-30 means it withstands damp heat and pollution degree 3 environments — typical for unheated enclosures in humid industrial halls.","metaTitle":"Schneider LC1E3210R6 Easy TeSys Contactor, 32A AC-3, 440V Co","metaDescription":"Obsolete Schneider LC1E3210R6 Easy TeSys Control contactor, 3P, 32A AC-3 at 440V, 440V 60Hz coil, 1NO aux. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2ec2c0f515d28d2b32eea08de2832946.pdf","sourceUrl":"https://www.se.com/ae/en/product/LC1E3210R6/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v32a440v-ac-coil60hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E3210R6/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to match for a replacement?","answer":"The critical specs are: three-pole, AC-3/AC-3e rated 32 A at ≤440 V, 440 V AC 60 Hz coil, and one normally open auxiliary contact. Any replacement must match these to drop into the same circuit without redesign."},{"question":"What compliance standards does this contactor meet?","answer":"It complies with EN/IEC 60947-1, 60947-4-1, 60947-5-1, and the corresponding GB/T 14048 series for the Chinese market. It also meets EN/IEC 60335-1 Clause 30.2 and 60335-2-40 Annex JJ for appliance applications, with fire resistance at 850 °C per IEC 60695-2-1."},{"question":"Can I mount this on a DIN rail?","answer":"Yes, the LC1E3210R6 supports both DIN rail and plate mounting. The 56 mm width fits standard 35 mm DIN rail, and the 86 mm depth leaves clearance for wiring in a standard enclosure."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E3210R6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E3210R6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}