{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E38004M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E38004M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E38004M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E38004M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control, LC1E38004M5WBIN, 4-pole contactor, 50 A AC-1 at 415 V, 220 V AC 50 Hz coil, IP20, DIN rail mount.","salesMarkdown":"Its headline rating is 50 A at up to 415 V AC — the current it can carry continuously in a resistive circuit without exceeding temperature limits. The four NO (normally-open) main poles close to make the load and open to break it, with an operating time of 12–22 ms on closing and 4–19 ms on opening. The coil is 220 V AC at 50 Hz, drawing 95 VA inrush at 20 °C. The 50 A AC-1 rating is the key selection number — it tells you the contactor can handle resistive loads (heaters, ovens, lighting banks) at that current. AC-1 is the least stressful duty; for motor loads (AC-3) the same contactor would be derated. The 56 mm width and 84 mm height fit standard panel layouts — plan for the 93 mm depth when the door clears. Connections are screw-clamp terminals: power circuit accepts up to 10 mm² flexible with cable end, control circuit up to 4 mm². Tightening torque is 2.1 N·m on the power side, 1.2 N·m on the control side.","metaTitle":"Schneider Electric LC1E38004M5WBIN Easy TeSys Contactor, 50","metaDescription":"Schneider Electric LC1E38004M5WBIN 4-pole contactor from the Easy TeSys range. Rated 50 A at 415 V AC-1 for resistive loads. Current production. IEC 60947 compliant. DIN rail mount","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 50 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 2.1 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"8000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","Associated fuse rating":"63 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...6 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 1.5...10 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1.5...10 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"304 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"4 NO","Product or component type":"Contactor","Irms rated making capacity":"380 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"5 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"50 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"60 A 40 °C - 600 s for power circuit 310 A 40 °C - 10 s for power circuit 150 A 40 °C - 60 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E38004M5WBIN/easy-tesys-contactor-4p-ctr-20a-ac14no220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E38004M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings I need to check for fit?","answer":"The headline rating is 50 A at 415 V AC under AC-1 utilisation category for resistive loads. The coil is 220 V AC 50 Hz. It has 4 NO main poles and no auxiliary contacts built in. Rated insulation voltage is 690 V. These are the numbers that govern fit for a BOM line."},{"question":"What compliance standards does this contactor meet?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-4-1, and EN/IEC 60947-5-1, plus the Chinese GB/T equivalents. Fire resistance is tested at 850 °C per IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068 for tropical environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E38004M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E38004M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}