{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E38008N5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E38008N5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E38008N5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E38008N5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E38008N5WBIN, 4-pole contactor, 50 A AC-1 rated operational current, 415 V AC 50 Hz control circuit, IP20, DIN rail or plate mount.","salesMarkdown":"## What the 50 A AC-1 rating means for your panel The LC1E38008N5WBIN is a 4-pole contactor from the Easy TeSys range, rated 50 A in AC-1 utilisation category at ≤ 415 V AC. AC-1 covers resistive loads — heaters, lighting banks, and non-inductive circuits where the current inrush is minimal. For motor duty (AC-3), you derate; this part is spec'd for resistive switching, not across-the-line motor starting. The 4-pole configuration gives 2 NO + 2 NC main poles, so you can switch a three-phase resistive load plus a neutral, or split the poles across two independent circuits. ## Control circuit and coil Pickup is guaranteed at 0.7 to 1.25 Uc; drop-out occurs between 0.3 and 0.6 Uc across -5 to 55 °C. Inrush power is 95 VA at 50 Hz, cos φ 0.75, at 20 °C. Heat dissipation from the control circuit runs 2 to 3 W. The operating time is 12 to 22 ms on closing, 4 to 19 ms on opening — fast enough for general switching but not for high-speed synchronisation. Dimensions are 93 mm deep, 56 mm wide, 84 mm tall — a compact footprint for a 4-pole 50 A contactor. Power-circuit terminals accept 1 to 10 mm² solid or 1 to 6 mm² flexible with cable end; control-circuit terminals take 1 to 4 mm². Tightening torque is 2.1 N·m for power, 1.2 N·m for control. The rated breaking capacity is 304 A at 440 V; the rated making capacity is 380 A at 440 V AC. Associated fuse recommendation is 63 A gG at ≤ 690 V, coordination type 1. Protective treatment is TH conforming to IEC 60068 for tropical environments.","metaTitle":"Schneider Electric Easy TeSys LC1E38008N5WBIN Contactor, 50","metaDescription":"Schneider Electric Easy TeSys LC1E38008N5WBIN 4-pole contactor. Rated 50 A AC-1 at 415 VAC. 415 VAC 50 Hz coil. Active production. DIN rail mount. Order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"93 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"12...22 ms on closing 4...19 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"2...3 W for control circuit","Mounting support":"DIN rail Plate","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"2.5 mOhm - Ith 50 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 2.1 N.m","Inrush power in VA":"95 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"8000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","Associated fuse rating":"63 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1800 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1...10 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1...6 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 1.5...10 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 1.5...10 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"304 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"380 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"5 W AC-1","[Uc] control circuit voltage":"415 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"50 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"8.5 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"60 A 40 °C - 600 s for power circuit 310 A 40 °C - 10 s for power circuit 150 A 40 °C - 60 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ba379087210343342ad2f83e26485cae.pdf","sourceUrl":"https://www.se.com/sg/en/product/LC1E38008N5WBIN/contactoreasy-tesys-controllc1e4p2no+2ncac1415v60ain415v50hz-wide-range/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E38008N5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"The key ratings are 50 A rated operational current in AC-1 at ≤ 415 V AC, 4-pole configuration with 2 NO + 2 NC, 415 V AC 50 Hz control coil, IP20 protection, and 350,000 electrical cycles in AC-1."},{"question":"What is the mounting option and physical size?","answer":"The contactor mounts on DIN rail or directly to a backplate. Dimensions are 93 mm deep, 56 mm wide, and 84 mm tall."},{"question":"What compliance documentation is available for this part?","answer":"The contactor is certified to EN/IEC 60947-1, -4-1, and -5-1, plus GB/T 14048.1.4, and.5. It carries TH protective treatment per IEC 60068 and fire resistance to 850 °C per IEC 60695-2-1. Specific RoHS, REACH, or UL documentation should be confirmed at the time of order against the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E38008N5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E38008N5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}