{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E3810F5","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E3810F5","canonicalUrl":"https://aoctrl.com/schneider/LC1E3810F5","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E3810F5","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys Control contactor, LC1E3810F5, 3P(3NO), AC-3/AC-3e ≤440V 38A, 110V AC 50Hz coil, 1NO auxiliary contact.","salesMarkdown":"## What the LC1E3810F5 is and what its ratings mean The Schneider Electric LC1E3810F5 is a three-pole contactor from the Easy TeSys Control range, rated for 38 A in AC-3 and AC-3e utilisation categories at ≤440 V. The AC-3e suffix means it's also certified for the higher electrical endurance demands of certain motor applications per IEC 60947-4-1. The coil is 110 V AC, 50 Hz, and the built-in auxiliary is one normally-open contact. The contactor carries a guaranteed non-overlap time of 1.5 ms between NC and NO contacts on both energisation and de-energisation. That timing is critical in reversing or star-delta starters where you need to ensure one set of power contacts is fully open before the other closes — a short-circuit condition otherwise. The 1.5 ms window is the guaranteed minimum, per the datasheet. ## Mounting and integration into a panel Mounts on either DIN rail or plate, so it fits standard panel layouts. Dimensions are 86 mm deep by 56 mm wide by 84 mm high — the 56 mm width is the same footprint as the classic TeSys D series, meaning it occupies one standard 9 mm pitch module's width on a DIN rail. The IP2X finger protection on the front face is what you expect for a panel-mounted contactor: it keeps incidental contact out but is not sealed against dust or moisture. The 55 °C upper limit is typical for contactors in a ventilated enclosure; if the panel ambient runs hotter, you need to derate the continuous current or add forced cooling. ## Standards compliance and environmental protection Also carries compliance with EN/IEC 60335-1 Clause 30.2 and -2-40 Annex JJ for glow-wire and fire resistance in household and HVAC equipment. The fire resistance is tested to 850 °C per IEC 60695-2-1. Protective treatment is TH (pollution degree 3) per IEC 60068-2-30, meaning it's suitable for environments with cyclic temperature and humidity variations.","metaTitle":"Schneider Electric LC1E3810F5 Easy TeSys Contactor, 38A AC-3","metaDescription":"Schneider Electric LC1E3810F5 Easy TeSys Control contactor, 3P, 38A AC-3/AC-3e at ≤440V, 110V AC 50Hz coil, 1NO aux. Active production. DIN rail/plate mount. EN/IEC 60947 compliant","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068-2-30 test Db","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2199eaac02920851eaa7561be9e82255.pdf","sourceUrl":"https://www.se.com/vn/en/product/LC1E3810F5/contactoreasy-tesys-controllc1e3p3noac3-ac3e440v38a110v-ac-coil50hz1no-auxiliary-contact/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E3810F5/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the LC1E3810F5?","answer":"Three-pole contactor rated 38 A in AC-3 and AC-3e at ≤440 V. Coil is 110 V AC, 50 Hz. Includes one normally-open auxiliary contact. Dimensions: 86 mm deep, 56 mm wide, 84 mm high. Mounts on DIN rail or plate."},{"question":"What standards does the LC1E3810F5 comply with?","answer":"Compliant with EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, and the GB/T equivalents. Also compliant with EN/IEC 60335-1 Clause 30.2 and EN/IEC 60335-2-40 Annex JJ for appliance applications. Fire resistance tested to 850 °C per IEC 60695-2-1."},{"question":"What is the operating temperature range for the LC1E3810F5?","answer":"Operating ambient is -5 to 55 °C. Storage range is -60 to 80 °C. The part operates without derating up to 3000 m altitude."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E3810F5","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E3810F5 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}