{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E40008M5WBIN","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E40008M5WBIN","canonicalUrl":"https://aoctrl.com/schneider/LC1E40008M5WBIN","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E40008M5WBIN","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E40008M5WBIN, 4-pole contactor, 75 A AC-1 at 415 V, 220 V AC 50 Hz coil, screw clamp terminals, IP20.","salesMarkdown":"For motor duty, you'd need the AC-3 rating, which this part does not list. The 75 A AC-1 rating at 40 °C ambient is the headline number. AC-1 covers resistive loads where the current is in phase with voltage — no high inrush like a motor. The rated breaking capacity is 320 A at 440 V, and the rated making capacity is 400 A at 440 V AC, both conforming to IEC 60947. That tells you the contactor can close onto and interrupt fault currents well above its continuous rating, which matters for coordination with upstream protection. The coil is 220 V AC 50 Hz, wide-range type, with a drop-out threshold of 0.3 to 0.6 Uc and an operational range of 0.7 to 1.25 Uc. Inrush power is 160 VA at 50 Hz, cos phi 0.75, at 20 °C. Steady-state heat dissipation for the control circuit runs 6 to 10 W. That's enough to matter in a densely packed panel — account for the thermal load when sizing the enclosure. Pole configuration is 2 NO + 2 NC, with no auxiliary contacts built in. If you need auxiliaries for status feedback or interlocking, you'll add them separately. Dimensions are 85 mm wide, 127 mm high, 110 mm deep — that's a compact footprint for a 75 A 4-pole contactor. Power circuit terminals accept solid or flexible cable: 2.5 to 25 mm² with a cable end, or 2.5 to 16 mm² solid. Tightening torque is 5 N.m on the power side, 1.2 N.m on the control side. The associated fuse rating for type 1 coordination is 80 A gG at up to 690 V. That's the maximum fuse you can put upstream and still have the contactor survive a short circuit without replacement. ## Durability and environmental specs Electrical durability is 350,000 cycles in AC-1 duty. Mechanical durability is 5 million cycles. That's a long service life for a resistive-load contactor — you'll likely retire the panel before the contactor wears out. Maximum operating rate is 1,200 cycles per hour at 60 °C. Operating altitude is 3,000 m without derating. Mechanical robustness: the contactor withstands 1.5 Gn vibration when open, 3 Gn when closed, and shocks of 6 Gn open, 7 Gn closed. Fire resistance is 850 °C conforming to IEC 60695-2-1. Protective treatment is TH conforming to IEC 60068, meaning it's protected against tropical humid conditions.","metaTitle":"LC1E40008M5WBIN Easy TeSys Contactor, 75 A AC-1, 4P","metaDescription":"Schneider Electric LC1E40008M5WBIN Easy TeSys contactor, 75 A rated operational current at 415 V AC-1, 4 poles (2 NO + 2 NC), 220 V AC 50 Hz coil. Active production. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"110 mm","Range":"Easy TeSys","Width":"85 mm","Height":"127 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5","Operating time":"20...26 ms on closing 8...12 ms on opening","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Heat dissipation":"6...10 W for control circuit","Mounting support":"Plate DIN rail","Pollution degree":"3","Range of product":"Easy TeSys Control","Average impedance":"1.5 mOhm - Ith 75 A 50 Hz for power circuit","Device short name":"LC1E","Poles description":"4P","Tightening torque":"Control circuit: 1.2 N.m Power circuit: 5 N.m","Inrush power in VA":"160 VA 50 Hz cos phi 0.75 (at 20 °C)","Operating altitude":"3000 m","Control circuit type":"AC at 50 Hz wide range","Overvoltage category":"III","Protective treatment":"TH conforming to IEC 60068","Utilisation category":"AC-1","Contactor application":"Resistive load","Electrical durability":"350000 cycles AC-1","Mechanical durability":"5000000 cycles","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)","Associated fuse rating":"80 A gG at <= 690 V coordination type 1 for power circuit","Maximum operating rate":"1200 cyc/h 60 °C","Connections - terminals":"Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 2.5...10 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid Power circuit: screw clamp terminals 1 2.5...25 mm² - cable stiffness: solid Power circuit: screw clamp terminals 2 2.5...16 mm² - cable stiffness: solid","IP degree of protection":"IP20 conforming to IEC 60529","Rated breaking capacity":"320 A at 440 V for power circuit conforming to IEC 60947","Pole contact composition":"2 NO + 2 NC","Product or component type":"Contactor","Irms rated making capacity":"400 A at 440 V AC for power circuit conforming to IEC 60947-4-1","Power dissipation per pole":"5.4 W AC-1","[Uc] control circuit voltage":"220 V AC 50 Hz","Auxiliary contact composition":"Without","[Ui] rated insulation voltage":"690 V conforming to IEC 60947-4-1","Control circuit voltage limits":"0.3...0.6 Uc (-5...55 °C):drop-out 50 Hz 0.7...1.25 Uc (-5...55 °C):operational 50 Hz","[Ie] rated operational current":"75 A (at <40 °C) at <= 415 V AC AC-1 for power circuit","[Ue] rated operational voltage":"Power circuit: <= 690 V AC 50/60 Hz","Hold-in power consumption in VA":"15 VA 50 Hz cos phi 0.3 (at 20 °C)","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947","[Icw] rated short-time withstand current":"320 A 40 °C - 10 s for power circuit 165 A 40 °C - 60 s for power circuit 72 A 40 °C - 600 s for power circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E40008M5WBIN/easy-tesys-contactor-4p-ctr-25a-ac12no+2nc220v-50hz-wb/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E40008M5WBIN/alternatives.json"},"ai":{"faq":[{"question":"What are the key specifications I need for a BOM check?","answer":"Rated operational current: 75 A at 415 V AC-1. Poles: 4 (2 NO + 2 NC). Coil: 220 V AC 50 Hz. Dimensions: 85 x 127 x 110 mm. Mounting: DIN rail or plate. Standards: IEC 60947-4-1. Associated fuse: 80 A gG at 690 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E40008M5WBIN","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E40008M5WBIN when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}