{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E40B10M7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E40B10M7","canonicalUrl":"https://aoctrl.com/schneider/LC1E40B10M7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E40B10M7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys contactor, LC1E40B10M7, 3-pole (3 NO), AC-3 rated 40 A at ≤ 440 V, 220 V AC coil, DIN-rail or plate mount.","salesMarkdown":"IP2X finger protection means it's safe for open panel work, but it's not a washdown part; keep it inside a cabinet. The AC-3 rating at 40 A covers most 15–18.5 kW motor loads at 400 V three-phase — that's the real-world current for starting and stopping a motor under load. AC-1 rating handles resistive loads up to the same current if you're switching heaters or lighting banks. The 1.5 ms non-overlap time between NC and NO contacts guarantees break-before-make, which matters for reversing or interlocking circuits where you can't let both coils energise at once.","metaTitle":"Schneider Electric LC1E40B10M7 Easy TeSys Contactor, 40A AC-","metaDescription":"Schneider Electric LC1E40B10M7 Easy TeSys contactor, 3-pole, 40A AC-3 at 440V, 220V AC coil. Active production. DIN-rail mount. Standards: EN/IEC 60947. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"DIN rail Plate","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E40B10M7/easy-tesys-contactor-3p3-no-ac3-440-v-40a-220-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E40B10M7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"AC-3 rating is 40 A at ≤ 440 V, with a 220 V AC coil. It's a 3-pole (3 NO) contactor, rated for motor control and resistive loads. Depth is 86 mm, width 56 mm, height 84 mm."},{"question":"What standards does the LC1E40B10M7 comply with?","answer":"It complies with EN/IEC 60947-1, -4-1, -5-1, and GB/T 14048.1.4.5. Fire resistance is tested to 850 °C per IEC 60695-2-1, and protective treatment is TH (pollution degree 3) per IEC 60068."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E40B10M7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E40B10M7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}