{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E40B10Q7","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E40B10Q7","canonicalUrl":"https://aoctrl.com/schneider/LC1E40B10Q7","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E40B10Q7","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy TeSys LC1E40B10Q7, 3-pole contactor, 40 A AC-3 at ≤440 V, 380 V AC coil, plate/DIN rail mount.","salesMarkdown":"Rated 40 A in AC-3 utilisation category at operational voltages up to 440 V, meaning it is sized for switching three-phase squirrel-cage induction motors under full-load starting conditions. The AC-3 rating is the governing figure for motor control applications; the contactor also carries AC-1 and AC-3e categories for resistive and enhanced motor loads respectively. The 380 V AC coil voltage is a specific control-circuit requirement. Verify that the existing control transformer or PLC output matches this nominal voltage, as the coil's operating range is tied to the -5...55 °C permissible ambient temperature at rated coil voltage (Uc). Mechanical robustness is specified for vibration and shock: 1.5 Gn (5...300 Hz) when open, 3 Gn when closed, and shock resistance of 10 Gn for 11 ms in the closed position. This qualifies the contactor for installation on machinery subject to moderate industrial vibration, such as conveyor drives or pump skids. This covers the product safety, performance, and coordination requirements for low-voltage switchgear and controlgear assemblies. For audit purposes, the datasheet provides the traceable certification basis. The IP2X degree of protection per IEC 60529 indicates finger-safe terminals but not washdown capability. Operates without derating up to 3000 m altitude. Above that, consult the thermal derating curve in the full technical documentation. Dimensions: 86 mm depth, 56 mm width, 84 mm height.","metaTitle":"Schneider Electric LC1E40B10Q7 Easy TeSys Contactor, 40A AC-","metaDescription":"Obsolete Schneider LC1E40B10Q7 Easy TeSys contactor. 3P, 40A AC-3 at 440V, 380V AC coil. Sourced to order against RFQ. EN/IEC 60947 compliant.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Contactors"],"specifications":{"Depth":"86 mm","Range":"Easy TeSys","Width":"56 mm","Height":"84 mm","Standards":"EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 GB/T 14048.1 GB/T 14048.4 GB/T 14048.5 EN/IEC 60335-1:Clause 30.2 EN/IEC 60335-2-40:Annex JJ","Fire resistance":"850 °C conforming to IEC 60695-2-1","lifecycle_stage":"current","Mounting support":"Plate DIN rail","Non-overlap time":"1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact","Range of product":"Easy TeSys Control","Device short name":"LC1E","Poles description":"3P","Operating altitude":"3000 m without derating","Protective treatment":"TH (pollution degree 3) conforming to IEC 60068","Utilisation category":"AC-3 AC-3e AC-1","Contactor application":"Motor control Resistive load","Mechanical robustness":"Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms)","IP degree of protection":"IP2X conforming to IEC 60529","Product or component type":"Contactor","[Ue] rated operational voltage":"Power circuit: 10 MOhm for control circuit","Permissible ambient air temperature around the device":"-20...70 °C at Uc -60...80 °C storage -5...55 °C operation"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/in/en/product/LC1E40B10Q7/easy-tesys-contactor-3p3-no-ac3-440-v-40a-380-v-ac-coil/","alternativesUrl":"https://aoctrl.com/api/mcp/products/LC1E40B10Q7/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"It is a 3-pole contactor rated 40 A in AC-3 (motor switching) at ≤440 V, with a 380 V AC coil. It also carries AC-1 and AC-3e utilisation categories."},{"question":"How should I source this obsolete part?","answer":"Submit an RFQ. As an obsolete item, it is not stocked in standard distribution and is sourced through independent surplus inventory on a per-order basis."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E40B10Q7","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E40B10Q7 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}