{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"LC1E50ADCH1S260N","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"LC1E50ADCH1S260N","canonicalUrl":"https://aoctrl.com/schneider/LC1E50ADCH1S260N","factsUrl":"https://aoctrl.com/api/mcp/products/LC1E50ADCH1S260N","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric, Easy TeSys Control, Contactor LC1E50ADCH1S260N, 1-pole, 50 A Ith, 12 V DC coil, 1000 V DC switching.","salesMarkdown":"## Ratings and application The LC1E50ADCH1S260N: The control circuit is 12 V DC (0.85–1.1 Uc operational range, dropout at 0.1–0.75 Uc) with a hold-in power consumption of 5.5 W. Mechanical durability is 300,000 cycles; electrical durability is tested at 750 V and 1000 V DC for breaking-only cycles at 50 A. The contactor is designed for resistive load switching — not inductive loads in DC motor circuits without external arc suppression. Short-time current capability extends to 75 A for 60 minutes, 100 A for 20 minutes, and 500 A for 0.6 seconds, giving headroom for transient overloads or weld suppression in DC applications. ## Physical and environmental Dimensions: 2.8 in height × 1.4 in width × 2.1 in depth. IP60 protection keeps out dust and incidental contact. Mounting is vertical support, with power circuit terminals accepting M5 nut, flat and spring washers; torque to 31–39.8 lbf·in (3.5–4.5 N·m). Control circuit has a 2-wire supply, 15.7 in (40 cm) flying leads. Ambient operating temperature spans –40 to 185 °F (–40 to 85 °C), with derating not required up to 4000 m altitude. Insulation resistance is 1000 MΩ at 1000 V DC; rated impulse withstand voltage (Uimp) 6 kV with coil not connected to power circuit, per IEC 60947.","metaTitle":"Schneider LC1E50ADCH1S260N Contactor, 12VDC, 50A","metaDescription":"Current production 1-pole DC contactor from Easy TeSys range. 50 A Ith, 12 VDC coil, 1000 V max switching. Sourced to order. Active lifecycle.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Contactors"],"specifications":{"Depth":"2.1 in (54.6 mm)","Range":"Easy TeSys","Width":"1.4 in (35.5 mm)","title":"LC1E50ADCH1S260N","Height":"2.8 in (70.1 mm)","Category":"US10I1222354","Polarity":"No main contact No coil","Standards":"IEC 60947-4-1 GB/T 14048.4","description":"Contactor for charging post,Easy TeSys Control,DC-1 <=1000V 50A,12V DC, single coil,epoxy,internal thread,without connector","Operating time":"50 ms on closing 30 ms on opening","lifecycle_stage":"current","Mounting Support":"Vertical support","Range of Product":"Easy TeSys Control","Average impedance":"2 mOhm - Ith 50 A","Device short name":"LC1E","Poles description":"1P","Tightening torque":"Power circuit 31.0...39.8 lbf.in (3.5...4.5 N.m)","Operating altitude":"13123.36 ft (4000 m) without derating","End Connection Type":"Internal Thread","Control circuit type":"DC","Contactor application":"Resistive load","Electrical durability":"1000 cycles at 750 V, 50 A on resistive load for only breaking, 0.6s open, 5.4s break 1000 cycles at 1000 V, 50 A on resistive load for only breaking, 0.6s open, 5.4s break","Insulation resistance":"1000 MOhm at 1000 V DC","Mechanical durability":"300000 cycles","Mechanical robustness":"Vibrations 5 g, 10...500 Hz) Shocks 20 g for 11 ms)","Nbr. of units in pkg.":"1","Connections - terminals":"Power circuit M5 nut Power circuit flat washers Power circuit spring washers Control circuit 2-wire supply 15.7 in (40 cm)","IP degree of protection":"IP60","Pole contact composition":"1 NO","Maximum switching voltage":"1000 V DC","Minimum switching current":"0.1 A","Minimum switching voltage":"8 V for DC","Product or Component Type":"Contactor","[Uc] control circuit voltage":"12 V DC","Auxiliary contact composition":"1 NO","Permissible short-time rating":"50 A for continuous 75 A 60 min 100 A 20 min 200 A 30 s 400 A 2 s 500 A 0.6 s","[Ui] rated insulation voltage":"1000 V IEC 60947-4-1 power circuit","Control circuit voltage limits":"0.85...1.1 Uc operational 0.1...0.75 Uc drop-out","Hold-in power consumption in W":"5.5 W","Ambient air temperature for operation":"-40...185 °F (-40...85 °C) operation -40...185 °F (-40...85 °C) storage","[Uimp] rated impulse withstand voltage":"6 kV coil not connected to the power circuit IEC 60947","[Ith] conventional free air thermal current":"50 A for power circuit"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$175.00","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/917e74bef93ae1f6d728db07cc91d326.pdf","sourceUrl":"https://www.se.com/us/en/product/LC1E50ADCH1S260N/contactor-for-charging-posteasy-tesys-controldc1-1000v-50a12v-dc-single-coilepoxyinternal-threadwithout-connector/"},"ai":{"faq":[{"question":"What is the coil voltage of this contactor?","answer":"The control circuit voltage is 12 V DC with a hold-in power of 5.5 W."},{"question":"What are the maximum switching ratings?","answer":"Maximum switching voltage is 1000 V DC; conventional free-air thermal current (Ith) is 50 A for the power circuit."},{"question":"What environmental conditions can this contactor withstand?","answer":"Operating temperature range –40 to 185 °F (–40 to 85 °C) with no derating up to 4000 m altitude. It is rated IP60 and can handle vibration 5 g (10–500 Hz) and shock 20 g for 11 ms."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/LC1E50ADCH1S260N","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/LC1E50ADCH1S260N when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}